MVI69L-MBS ♦ Platform
Configuring the MVI69L-MBS Using PCB
Modbus Serial Lite Communication Module
User Manual
ProSoft Technology, Inc.
Page 51 of 130
Modbus
Function
1,2,3,4,5,6,15
,16
Specifies the Modbus function to be executed.
1
– Read Coil Status (0xxxx)
2
– Read Input Status (1xxxx)
3
– Read Holding Registers (4xxxx)
4
– Read Input Registers (3xxxx)
5
– Force (Write Single) Coil (0xxxx)
6
– Force (Write Single) Holding Register (4xxxx)
15
– Preset (Write) Multiple Coils (0xxxx)
16
– Preset (Write) Multiple Registers (4xxxx)
MB Address in
Device
0 to 65535
Specifies the register or digital point address offset within the Modbus
slave device. The MBS Master reads or writes from/to this address
within the slave.
Refer to the documentation of each Modbus slave device for their
register and digital point address assignments.
Note: The value entered here does not need to include the "Modbus
Prefix" addressing scheme. Also, this value is an offset of the zero-
based Modbus addressing scheme.
Example: Using a Modbus Function Code 3 to read from address
40010 in the slave, a value of ‘9’ would be entered in this parameter.
The firmware (internally) adds a ‘40001’ offset to the value entered.
This is the same for all Modbus addresses (0x, 1x, 3x, 4x).
Override
Value Upon
Error
This parameter is only applicable for
Enable Codes
3 (Bit/Word
Override) or 4 (Float Override).
If an error occurs associated to a read command the module
automatically populates the associated database area with this
override value.
Comment
32-character text field.
3.2.4 Ethernet 1
This section defines the permanent IP address, Subnet Mask, and Gateway of
the module.
In the ProSoft Configuration Builder tree view, double-click the
E
THERNET
1
icon.
Parameter
Description
IP Address
Unique IP address assigned to the module
Netmask
Subnet mask of module
Gateway
Gateway (if used)