WAGO-TO-PASS® 761
WAGO TO-PASS® Web 125
761-216 TO-PASS® Compact, 8 AI, Web, MODBUS
Manual
Version 2.0.0
10.3.2.3 Logger Script FW 2.33 (Counter Inputs)
The counter inputs have resulted in counter data and an indicator being added to
the display for non-set time (operating hours) to the logger script ("LV=02.01").
Example:
&HT=1
(same as for Value Script)
&LCD2=0;0;e;20F5800;d;0;0;0
10.3.2.3.1 Data Format of an LCDx Variable
Table 59: Data format, logger script extension, Variable LCDx
Index Contents
Format
0
Counter status 1st input
Status 1
1
Counter value 1st input, hexadecimal Value > 8
2
Counter status 2nd input
Status 1
3
Counter value 2nd input, hexadecimal Value > 8
4
Counter status 3rd input
Status 1
5
Counter value 3rd input, hexadecimal Value > 8
6
Counter status 4th input
Status 1
7
Counter value 4th input, hexadecimal Value > 8
The counter status can assume the statuses indicated by the transmitted SMS:
Table 60: Counter status
Status Explanation
0
Digital input not configured as a counter.
e
Counter is active.
d
Counter is not active.
o
Counter overflow.
r
Counter has been reset.
s
Counter has been started.
c
Counter value has been changed.
The counter status shows the last change that has occurred since the last logger
script transmission, or after a system start (independent of the SMS and value
status).
&HT=1: (value always 1) the device time has not been set (&TI entry is operating
hours information, started on 01.01.00 at 00:00:00), otherwise this entry is not
present.