4.6 Diagnostic and interrupt
Event
Process interrupt
Diagnostics
interrupt
parameterizable
HW gate open
X
-
X
HW gate closed
X
-
X
Overflow
X
-
X
Underflow
X
-
X
Comparison value
X
-
X
End value
X
-
X
Latch value
X
-
X
Diagnostics buffer overflow
-
X
-
Process interrupt lost
-
X
X
Overload at output
-
X
X
So you may react to asynchronous events, there is the possibility to
activate a process interrupt. A process interrupt interrupts the linear
program sequence and jumps depending on the master system to a
corresponding Interrupt routine. Here you can react to the process
interrupt accordingly.
With CANopen the process interrupt data a transferred via an emer-
gency telegram.
Operating with CPU, PROFIBUS and PROFINET the process inter-
rupt data were transferred via diagnostics telegram.
SX - Subindex (5000h) for access via EtherCAT
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default SX
PRIT_A
1
Process interrupt data
00h
02h
PRIT_B
1
State of the inputs
00h
03h
PRIT_US 2
µs ticker
00h
04h ...
05h
Byte
Bit 7 ... 0
0
Process interrupt data
n
Bit 0: HW gate opened
n
Bit 1: HW gate closed
n
Bit 2: Overflow, underflow or end value reached
n
Bit 3: Comparison value reached
n
Bit 4: Latch value reached
n
Bit 7 ... 5 reserved
Overview
Process interrupt
PRIT_A Process inter-
rupt data
VIPA System SLIO FM 050
Deployment
Diagnostic and interrupt
HB300 | FM | 050-1BA00 | GB | 15-11
60