QUAD Plus
Technical Support:
10
14, 44, 74, 104
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Basic Setpoint
Reference Setpoint
15, 45, 75, 105
1 Bit
I
C - - W -
DPT_Step
0/1
[Tx] Setpoint Step
0 = -0.5ºC; 1 = +0.5ºC
16, 46, 76, 106
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 -
670760.00
[Tx] Setpoint Offset
Float Offset Value
17, 47, 77, 107
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Setpoint Status
Current Setpoint
18, 48, 78, 108
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Basic Setpoint Status
Current Basic Setpoint
19, 49, 79, 109
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 -
670760.00
[Tx] Setpoint Offset Status
Current Setpoint Offset
20, 50, 80, 110
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Offset Reset
Reset offset
21, 51, 81, 111
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
22, 52, 82, 112
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
23, 53, 83, 113
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
24, 54, 84, 114
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
25, 55, 85, 115
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Cool)
PI Control (Continuous)
26, 56, 86, 116
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Heat)
PI Control (Continuous)
27, 57, 87, 117
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
PI Control (PWM)
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
2-Point Control
28, 58, 88, 118
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
PI Control (PWM)
29, 59, 89, 119
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Cool
Temp >= (SBand) => "1"
30, 60, 90, 120
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Heat
Temp <= (Setpoint-Band) => "1"
31, 61, 91, 121
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] PI State (Cool)
0 = PI signal 0%; 1 = PI signal greater than 0%
32, 62, 92, 122
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] PI State (Heat)
0 = PI signal 0%; 1 = PI signal greater than 0%
123, 127, 131, 135
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[Ix] Current Temperature
Temperature sensor value
124, 128, 132, 136
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm; 1 = Alarm
125, 129, 133, 137
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm; 1 = Alarm
126, 130, 134, 138
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm; 1 = Alarm
139, 145, 151, 157
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] Input Lock
1 = Locked; 0 = Unlocked
140, 146, 152, 158
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Short Press] 0
Sending of 0
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Short Press] 1
Sending of 1
1 Bit
I
C T - W -
DPT_Switch
0/1
[Ix] [Short Press] 0/1 Switching
Switching 0/1