QUAD Plus
Technical Support:
9
ANNEX I. COMMUNICATION OBJECTS
“
Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning
because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
2
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
3, 33, 63, 93
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Temperature Source 1
External Sensor Temperature
4, 34, 64, 94
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Temperature Source 2
External Sensor Temperature
5, 35, 65, 95
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[Tx] Effective Temperature
Effective Control Temperature
6, 36, 66, 96
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode
1-byte HVAC Mode
7, 37, 67, 97
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: comfort
0 = Off; 1 = On
8, 38, 68, 98
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: standby
0 = Off; 1 = On
9, 39, 69, 99
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: economy
0 = Off; 1 = On
10, 40, 70, 100
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: protection
0 = Off; 1 = On
11, 41, 71, 101
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (input)
0 = Closed; 1 = Open
12, 42, 72, 102
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
13, 43, 73, 103
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode Status
1-byte HVAC Mode