Parameter List/Record
A-7
Parameter 50 “Trend 1 Input” to Parameter 104 “Final Vel Ref”
Parameter 51 “Trend 2 Input” to Parameter 106 “Velocity Fdbk”
The sample period for the trend files will be programmed to 10 secs per data
point. The thermal time constant of most motors is quite large, the operating
parameters will be captured for 16 minutes prior to the occurrence of the
fault. The trigger will be programmed to occur when the fault occurs, the
fault will be reported in Parameter 101 “Drive Fault” bit 5. All 100 data
samples will be taken prior to the trigger. The necessary set-up parameter
values for Trend File 1 Are:
Parameter 904“Trend Logic Val” = 00000000000100000 (bit sel)
Parameter 910 “Tr1 Opnd Param X” = 104 (test operand)
Parameter 911 “Tr1 Opnd Param Y” = 904 (constant operand)
Parameter 912 “Tr1 Operator” =.EQ. (operator for bit 5)
Parameter 913 “Tr1 Sample Rate” = 10 (sample rate in sec)
Parameter 914 “Tr1 Post Samples” = 0 (# samples after trig)
Parameter 915 “Tr1 Mult Trigger” = OFF (single shot)
Parameter 916 “Tr1 Enable” = ON (enable trend)
653
DESIRED CONTOUR
657
DROOP PERCENT
658
DROOP FILTER
659
KI VELOCITY LOOP
660
KP VELOCITY LOOP
661
KF VELOCITY LOOP
663
FORWARD BRIDGE CURRENT LIMIT
664
REVERSE BRIDGE CURRENT LIMIT
665
START TAPER SPEED
666
END TAPER SPEED
667
MIN TAPER CURRENT
668
di/dt LIMIT
669
SLAVE PERCENT
672
KI FLUX
673
KP FLUX
674
FIELD ECONOMY REFERENCE
675
FIELD ECONOMY DELAY
676
FIELD FLUX REFERENCE
677
FIELD CURRENT AT 0/8 FLUX
678
FIELD CURRENT AT 1/8 FLUX
679
FIELD CURRENT AT 2/8 FLUX
680
FIELD CURRENT AT 3/8 FLUX
681
FIELD CURRENT AT 4/8 FLUX
682
FIELD CURRENT AT 5/8 FLUX
683
FIELD CURRENT AT 6/8 FLUX
684
FIELD CURRENT AT 7/8 FLUX
685
FIELD CURRENT AT 1/0 FLUX
Parameter
Number
Description
Value
PLC Reference
Aotewell Ltd industry-mall.net
www.aotewell.com
sales@aotewell.com
www.aotewell.com