Commissioning
EL3773
101
Version: 2.5
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
> 32 <
1C33:01
Sync mode
Current synchronization mode:
• Bit 0 = 0: Free Run
• Bit 0 = 1: Synchron with SM 2 Event
• Bit 0-1 = 11: DC with SYNC1 event
• Bit 15 = 1: Fast Mode
UINT16
RW
0x0002 (2
dec
)
1C33:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle
time
• DC-Mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x003D0900
(4000000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:04
Sync modes supported Supported synchronization modes:
• Bit 0 = 1: Free Run
• Bit 1 = 1: Synchron with SM 2 Event (Outputs
available
• Bit 2 = 1: DC-Mode (SYNC0)
• Bit 3 = 1: DC-Mode (SYNC1)
• Bit 12 = 1: Legacy Synchron
• Bit 13 = 1: SM event
• Bit 14 = 1: dynamic times (measure by writing
• Bit 15 = 1: Fast Mode
UINT16
RO
0x0806
(2054
dec
)
1C33:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x000186A0
(100000
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:08
Command
With this entry the real required process data provision
time can be measured.
• 0: Measurement of the local cycle time is
stopped
• 1: Measurement of the local cycle time is
started
The entries
,
are updated with the maximum mea-
sured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum Delay time
Time between SYNC1 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RO
FALSE
Index F000 Modular device profile
Index (hex) Name
Meaning
Data type
Flags
Default
F000:0
Modular device profile General information for the modular device profile
UINT8
RO
> 2 <
F000:01
Module index distance Index distance of the objects of the individual channels UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RO
0x0007 (7
dec
)
Summary of Contents for EL3773
Page 1: ...Documentation EL3773 Power Monitoring Oversampling Terminal 2 5 2018 03 13 Version Date...
Page 2: ......
Page 6: ...Table of contents EL3773 6 Version 2 5...
Page 39: ...Mounting and wiring EL3773 39 Version 2 5 Fig 29 Other installation positions...
Page 41: ...Mounting and wiring EL3773 41 Version 2 5 Fig 31 Block diagram...
Page 47: ...Commissioning EL3773 47 Version 2 5 Fig 38 Incorrect driver settings for the Ethernet port...
Page 147: ...Commissioning EL3773 147 Version 2 5 Fig 168 Confirming program start...