Software Configuration
Chapter 4
10/11/18
Bedrock Secure OSA Remote User Manual - BRDOC020_001
35
The bit definitions for the Input Analog Status mapped variable indicate status
as shown in Table 4-8. This status information is applicable when an OSA
Remote channel is configured for analog input or analog output. When an OSA
Remote channel is configured for discrete output, bit 4 of the status word
indicates that the output is above the calibrated range.
Serial Port Parameters
Parameters that are configurable in the Bedrock IDE for the OSA Remote serial
port are shown in Figure 4-4 and summarized in Table 4-9.
Input Analog Timestamp
DT (seconds)
DWORD (nanoseconds)
analog output, analog input, digital output, NAMUR
Output Analog
REAL
analog output
Requested Digital Values
WORD
digital output
Input Digital Values
WORD
digital input, digital output, NAMUR
Output Digital Values
WORD
digital output
Input Voltage
REAL
Measured voltage input into the OSA Remote.
Not specific to an individual channel or operating mode
IO Temperature
REAL
Measured temperature of the OSA Remote I/O
subsystem
Not specific to an individual channel or operating mode
Table 4-7 OSA Remote Mapped Variables
Variable
Type
Applies to Operating Mode(s) with
the Listed Functionality
Table 4-8 Input Analog Status Bit Definitions
Bit Number (Hex Value)
Meaning
Bit 0 (0x0001)
out of service
Bit 1 (0x0002)
communication failure
Bit 2 (0x0004)
A/D converter out of range
Bit 3 (0x0008)
analog value is outside the calibrated range
Bit 4 (0x0010)
input is above the calibrated range
Bit 5 (0x0020)
not used
Bit 6 (0x0040)
input is below the calibrated range
Bit 7 (0x0080)
module is in fail-safe mode