background image

20

21

Index

Data

Description

Byte

Read/write

12

End of closing  

temporised zone

0 to 100 % 

(lower than start value)

1

read / write

13

Start of opening  

temporised zone

0 to100 %

1

read / write

14

End of opening  

temporised zone

0 to 100 %  

(higher than start value)

1

read / write

15

Timer open time expected

in seconds

2

read / write

16

Timer close time expected

in seconds

2

read / write

17

Operating time without timer

in seconds

2

read / write

18

User pass word

ASCII characters 

«000» to «999»

3

read / write

19

Valve tag number 

ASCII characters 

ex: «MOV55VV»

8

read / write

20

Open breakout torque setting

40 to 100%, 101% if no limitation

1

read / write

21

Close tight torque setting

40 to 100%

1

read / write

22

Opening torque setting

40 to 100%

read / write

23

Closing torque setting

40 to 100%

read / write

24

Reset partial running time

0= no, 1= yes

write

25

Reset partial number of starts 0= no, 1= yes

write

26

Operating class

1: On – Off

2: Modulating Classe III

3 : Modulating Classe II

read only

27

Motor supply type

0: 3 phase 

1: single phase or DC

read only

28

Closing mode

0: close on  position

1: close on torque

3: open and close on torque

read only

29

Stroke unit

1: number of turns

2: degrees

3: mm

read only

30

Nut thread

(If linear system)

In mm (To calculate the stroke  

but only during set-up).  

Value is zero if no linear system.

read only

31

Locked motor timing

In seconds

1

read only

32

Reverse delay time

(unit 50ms) 

ex. 3 = 150ms

1

read only

33

External gear ratio

(format: 1/   ) 

ex 200 = 1/200

2

read only

34

Stroke measured during set-up For stroke unit see index 29

2

read only

35

Software version

ASCII characters  ex:1.03

6

read only

36

Manufacture date

ASCII characters

12

read only

37

Actuator number

ASCII characters

16

read only

38

Opening torque curve

Torque in %.

 

Data 1 = closed position

 

Data 2= 1% open

 

Data 101= 100% open

101

read only

Index

Data

Description

Byte

Read/write

39

Closing torque curve

Torque in %.

 

Data 1 = closed position

 

Data 2= 1% open

 

Data 101= 100% open

101

read only

40

Profibus slave address

1-125

1

read only

41

Indication address 0

Replicate the data  

of the cyclic register

1

read only

42

Indication address 1

Replicate the data  

of the cyclic register

1

read only

43

Indication address 2

Replicate the data  

of the cyclic register

1

read only

44

Indication address 3

Replicate the data  

of the cyclic register

1

read only

45

Indication address 4

Replicate the data  

of the cyclic register

1

read only

46

Indication address 5

Replicate the data  

of the cyclic register

1

read only

47

Indication address 6

Replicate the data  

of the cyclic register

1

read only

48

Indication address 7

Replicate the data  

of the cyclic register

1

read only

49

Indication address 8

Replicate the data  

of the cyclic register

1

read only

50

Indication address 9

Replicate the data  

of the cyclic register

1

read only

51

Indication address 10

Replicate the data  

of the cyclic register

1

read only

52

Indication address 11

Replicate the data  

of the cyclic register

1

read only

53

Indication address 12 -13

Replicate the data  

of the cyclic register

2

read only

54

Indication address 14-17

Replicate the data  

of the cyclic register

4

read only

55

Indication address 18-21

Replicate the data  

of the cyclic register

4

read only

56

Indication address 22-25

Replicate the data  

of the cyclic register

4

read only

57

Indication address 26-29

Replicate the data  

of the cyclic register

4

read only

58

Indication address 30-31

Replicate the data  

of the cyclic register

2

read only

59

Indication address 32

Replicate the data  

of the cyclic register

1

read only

60

Partial stroke %

1 to 100%

1

read/write

61

Partial stroke start position

0=close, 1=open

1

read/write

Summary of Contents for Intellibus

Page 1: ...instructions for start up INTELLIBUS PROFIBUS DP FOR INTELLI Intelli 2801 A1150 ...

Page 2: ...ring RedCom with redundancy extensions that can be used if the PLC can support the same extensions According to the fieldbus version required an INTELLIBUS single or redundant line may equip the actuator Control box with inside Profibus DP interface could be supplied to connect other equipment Please make sure to get and read the INTELLI instructions for start up ref NR1151 prior going further wit...

Page 3: ... cross Redundant channel No data exchange empty square Channel 1 is primary and on data exchange rotating triangle Channel 2 is backup and on data exchange alternative up and down triangle Channel 1 Intellibus module fault blinking cross Channel 2 is primary and on data exchange rotating triangle 3 2 Cabletype Use exclusively special PROFIBUS cable conforms to the EN50170 2 standard and of type A ...

Page 4: ...s on No ramifications 3 6 Emergencysupply The actuator INTELLI is normally supplied by the mains but in case of loss of power supply an emergency supply could be used to continue to communicate through the fieldbus This emergency supply needs 24V DC 4W 3 7 ProfibusDParchitecture Single line The Profibus cable coming from the PLC is connected to the first actuator then the Profibus cable links this...

Page 5: ...ommunication The cyclic communication is mainly use for the Process Data are read and written in a well defined timing The useful data are selected in the list below and transmitted in a cyclic way The selection of only a few data also increases the communication speed The acyclic communication is mainly use for maintenance The data are collected only on request that avoid to reduce the cyclic com...

Page 6: ... between proportional and ON OFF control assign an auxiliary command to the function AUTO ON OFF then select the control mode required from the control room see above Address 1 Address 4 Relay output option The relays could be used to have an output indication wired as a non fieldbus actuator or to drive outside devices through Profibus These optional relays could be configured in Intelli menu for...

Page 7: ...g closing direction of rotation discrepant BATTERY LOW OR IS NOT PRESENT In case of battery option the battery should be replaced because of too low voltage or the battery is missing Address 3 Running torque in RUNNING TORQUE Indication of the instantaneous torque 100 is the maximum actuator rated torque Address 4 Actuator position feedback ACTUATOR POSITION FEEDBACK 0 closed 100 open Bit n Value ...

Page 8: ... Bit n Value Description Bit 0 0 NO INDICATION 1 1 INDICATION 1 IS ACTIVE OPTION Bit 1 0 NO INDICATION 2 1 INDICATION 2 IS ACTIVE OPTION Bit 2 0 NO INDICATION 3 1 INDICATION 3 IS ACTIVE OPTION Bit 3 0 NO INDICATION 4 1 INDICATION 4 IS ACTIVE OPTION Bit 4 0 NO INDICATION 5 1 INDICATION 5 IS ACTIVE ESD INPUT BY DEFAULT Bit 5 0 NO VALVE JAMMED ALARM 1 VALVE JAMMED Bit 6 0 NO AUXILIARY 24V FAULT ALARM...

Page 9: ...ures since actuator manufacturing Address 18 to 21 Running time TOTAL RUNNING TIME To obtain the accumulated figures since actuator manufacturing Unit is 1 10 sec Address 22 to 25 Partial number of starts PARTIAL NUMBER OF STARTS Number of starts since the last reset Address 26 to 29 Partial running time PARTIAL RUNNING TIME Total running time since the last reset Unit is 1 10 sec Address 30 and 3...

Page 10: ...er line AvailabledatathroughPROFIBUSacycliccommunication Data is organised in slot and index Slot 0 Indexes 0 to 61 are listed below Index Data Description Byte Read write 0 Set up for auxiliary command 1 0 not used 1 local 0 remote 1 2 local remote 0 remote 1 3 local command inhibit 1 4 open inhibit 1 5 close inhibit 1 6 ON OFF 0 AUTO 1 7 fieldbus emergency closing 1 8 fieldbus emergency opening ...

Page 11: ...torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only Index Data Description Byte Read write 39 Closing torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only 40 Profibus slave address 1 125 1 read only 41 Indication address 0 Replicate the data of the cyclic register 1 read only 42 Indication address 1 Replicate the data o...

Page 12: ... 4 39 80 726 MOROCCO AQUATEL sarl aquatel wanadoo net ma CASABLANCA Tel 212 22 66 55 71 NETHERLANDS BERNARD CONTROLS BENELUX NV hans nobels bernardcontrols com AN ZWAAG Tel 31 0 229 298083 NEW ZEALAND MRCTransmark NZ LTD bill sunley mrctransmark com Auckland Tel 64 9 276 4149 NORWAY KSB LINDFLATEN AS firmapost lindflaten no LYSAKER Tel 476 71 29 900 POLAND MARCO matzanke pol pl WARSAW Tel 48 22 86...

Reviews: