43
Configuration and adjustment variables
(1) Note: The "Preset speeds" function may be incompatible with other functions (see page
).
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11402
2054 / 3
PS4
R/WS
4 preset speeds
Factory setting: if tCC = 1: 0 if tCC = 0 or 2: 132
Selecting the assigned logic input activates the function (1).
Check that PS2 has been assigned before assigning PS4.
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
If LAC = L3, the following assignments are possible:
171 = "Cd11": bit 11 of the CMD control word (page
) written by Modbus or CANopen
172 = "Cd12": bit 12 of the CMD control word (page
) written by Modbus or CANopen
173 = "Cd13": bit 13 of the CMD control word (page
) written by Modbus or CANopen
174 = "Cd14": bit 14 of the CMD control word (page
) written by Modbus or CANopen
175 = "Cd15": bit 15 of the CMD control word (page
) written by Modbus or CANopen
11403
2054 / 4
PS8
R/WS
8 preset speeds
Factory setting: 0
Selecting the assigned logic input activates the function (1).
Check that PS4 has been assigned before assigning PS8.
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
If LAC = L3, the following assignments are possible:
171 = "Cd11": bit 11 of the CMD control word (page
) written by Modbus or CANopen
172 = "Cd12": bit 12 of the CMD control word (page
) written by Modbus or CANopen
173 = "Cd13": bit 13 of the CMD control word (page
) written by Modbus or CANopen
174 = "Cd14": bit 14 of the CMD control word (page
) written by Modbus or CANopen
175 = "Cd15": bit 15 of the CMD control word (page
) written by Modbus or CANopen
11404
2054 / 5
PS16
R/WS
16 preset speeds
Factory setting: 0
Selecting the assigned logic input activates the function (1).
Check that PS8 has been assigned before assigning PS16.
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
If LAC = L3, the following assignments are possible:
171 = "Cd11": bit 11 of the CMD control word (page
) written by Modbus or CANopen
172 = "Cd12": bit 12 of the CMD control word (page
) written by Modbus or CANopen
173 = "Cd13": bit 13 of the CMD control word (page
) written by Modbus or CANopen
174 = "Cd14": bit 14 of the CMD control word (page
) written by Modbus or CANopen
175 = "Cd15": bit 15 of the CMD control word (page
) written by Modbus or CANopen