10. Menu (Group) Setting Description
◼
Program Group (G.PRG)
10. Program Menu (PROG)
●
Pattern Number Select
●
Wait Zone (WZ) Setting
●
Segment Number Select
●
Wait Zone Time Setting
• NP200 can program 30 patterns and 300 segments.
• NP200 stores a maximum of 300 segments in 10 patterns (maximum 99 segments per pattern).
• Each pattern consists of 99 segments and 0 (SEG=0).
WZ (Wait Zone) : This sets the deviation range of the PV from the SV.
1) Segment (SEG) =0
The pattern of Segment (SEG)=0 is to set:
Start condition (SSV, STC): SSV → Start set Value, STC → Start code
End condition (END.SEG, END.MOD, END.TM, and LINK.PT)
WAIT condition (WTM, WZ)
Time Signal Mode (TS.MD : TIME SIGNAL MODE)
Number of Repeat (REPEAT)
2) Segment (SEG) =1~99
The pattern of Segment (SEG)=1~99 is to set.
Operating PID Group Number (PIDNO), Set Value (SV), Time (TM), Time Signal (TS, TS.ON, and TS.OFF)
If PV fails to enter into WZ, the Wait function will infinitely repeat. To avoid this problem, WTM (Wait Time)
needs to be set. The wait function delays the start of the next program segment until the PV reaches
within a specified deviation range from the SP, or until the Wait Time has expired.
It is not guaranteed that there is no deviation between SV and PV before starting the next program
segment. The wait function will be enabled to prevent problems caused by large deviation.
The wait function can be applicable to all program segments.
WAIT ZONE (WZ) sets the deviation value used for the wait function (If WTM=OFF, Wait Time is infinite.)
When set, a running program will not move to the next segment until the PV enters into the WZ.
When OFF, the wait function will not be enabled –a running program will move to the next segment even
the PV fails to enter into the WZ.