Addr Description
Unit
Scaling
R/W Range
Data-Type
4x0001 Type
1
R
9710 = 1 x 1250Pa
9720 = 1 x 2500Pa
9750 = 1 x 5500Pa
9770 = 1 x 7000Pa
9711 = 2 x 1250Pa
9712 = 1 x 1 x 2500Pa
9717 = 1 x 1 x 7000Pa
9722 = 2 x 2500Pa
9777 = 2 x 7000Pa
uint16_t
4x0002
Error Code
1
R
See table "Fault correction"
uint16_t
4x0003
Analog output coupling
1
R/W
0 = analog output coupled with differential
pressure sensors = default
1 = analog output coupled as defined in
4x0028/4x0058 (setpoint)
uint16_t
4x0004
Differential pressure 1- Reliability
1
R
See table "Fault correction"
uint16_t
4x0005
Differential pressure 1 - Value
see config
R
uint16_t
4x0006 Differential pressure 2 - Reliability
1
R
See table "Fault correction"
uint16_t
4x0007 Differential pressure 2 - Value
see config
R
uint16_t
4x0008 Analog input 1 - Reliability
1
R
See table "Fault correction"
uint16_t
4x0009
Analog input 1 - Value
°C / mV
0.1 / 1
R
int16_t
4x0010 Analog input 2 - Reliability
1
R
See table "Fault correction"
uint16_t
4x0011
Analog input 2 - Value
°C / mV
0.1 / 1
R
int16_t
4x0015
Save mode time out
1
R/W
0=deactivated; 1=activated (60s) = default
int16_t
4x9014
Firmware version
1
R
int16_t
4x0020
Reliability
1
R
See table "Fault correction"
uint16_t
4x0021 Value
°C / mV
0.1 / 1
R
int16_t
4x0022
Sensortype AI1
1
R/W
0 = no Sensor = default
1 = PT1000
2 = LG-Ni 1000
3 = NTC 10k
4 = NI 1000
5 = 0…10V
uint16_t
4x0027
Value
mV
1
R/W
0 ≤ VAL ≤ 10500
uint16_t
4x0028 Dependence
1
R/W
0 = value @ 4x0027 = default if 4x0003=1
1 = with Analog input 1
2 = with Analog input 2
3 = with pressure sensor 1 = default if
4x0003=0
4 = with pressure sensor 2
uint16_t
4x0029
Scaling low - (0.0V)
mV
1
R/W
0 ≤ VAL < Scaling high (0 = default)
uint16_t
4x0030
Scaling high - (10.0V)
mV
1
R/W
Scaling low < VAL (10000 = default)
uint16_t
4x0035
Reliability
1
R
See table "Fault correction"
uint16_t
4x0036 Value
1
R
uint16_t
4x0037 Unit
1
R/W
0 = Pa = default
1 = PSI
2 = mmHG
3 = mmH2O
uint16_t
4x0038
Value [Pa]
Pa
1
R
uint16_t
4x0039
Value [PSI]
PSI
0.0001
R
uint16_t
4x0040
Zero point calibration
1
R/W
0 = no action
1 = zero point calibration P1+P2
2 = zero point calibration P2
3 = zero point reset to factory setting
P1+P2
4 = zero point reset to factory setting P2
uint16_t
4x0041
Sensor 1 full scale value
Pa
1
R
uint16_t
4x0042
Average 500 ms
R
uint16_t
Analog input 1
Analog output 1
Differential pressure sensor 1
see config #4x0037
4x0044
Average 4000 ms
R
uint16_t
4x0045
Average 16000 ms
R
uint16_t
4x0050
Reliability
1
R
See table "Fault correction"
uint16_t
4x0051 Value
°C/mV
0.1/1
R
int16_t
4x0052 Sensortype AI2
1
R/W
0 = no Sensor = default
1 = PT1000
2 = LG-Ni 1000
3 = NTC 10k
4 = NI 1000
5 = 0…10V
uint16_t
4x0057
Value
mV
1
R/W
0 ≤ VAL ≤ 10000
uint16_t
4x0058 Dependence
1
R/W
0 = value @ 4x0057 = default if 4x0003=1
1 = with Analog input 1
2 = with Analog input 2
3 = with pressure sensor 1
4 = with pressure sensor 2 = default if
4x0003=0
uint16_t
4x0059
Scaling low - (0V)
mV
1
R/W
0 ≤ VAL < Scaling high (0 = default)
uint16_t
4x0060
Scaling high - (10V)
mV
1
R/W
Scaling low < VAL (10000 = default)
uint16_t
4x0065
Reliability
1
R
See table "Fault correction"
uint16_t
4x0066 Value
1
R
uint16_t
4x0067 Unit
1
R/W
0 = Pa = default
1 = PSI
2 = mmHG
3 = mmH2O
uint16_t
4x0068
Value [Pa]
Pa
1
R
uint16_t
4x0069
Value [PSI]
PSI
0.0001
R
uint16_t
4x0070
Zero point calibration
1
R/W
0 =
no
action
1 = zero
point
calibration
P
1+P2
2 = zero point calibration P
2
3 = zer
o point reset to
factor
y
setting
P1+P2
4 = zero
point reset to
factory
setting P
2
uint16_t
4x0071
Sensor 2 full scale value
Pa
1
R
uint16_t
4x0072
Average 500 ms
R
uint16_t
4x0073
Average 1000 ms
R
uint16_t
4x0074
Average 4000 ms
R
uint16_t
4x0075
Average 16000 ms
R
uint16_t
4x0081
Flow low
0.01
R
uint16_t
4x0082
Flow high
0.01
R
uint16_t
4x0083
k factor
1
R/W
0 ≤ VAL ≤ 1500
uint16_t
4x0084 Unit
1
R/W
0 = m3/h = default
1 = m3/s
2 = l/s
uint16_t
4x0091
Flow low
0.01
R
uint16_t
4x0092
Flow high
0.01
R
uint16_t
4x0093
k factor
1
R/W
0 ≤ VAL ≤ 1500
uint16_t
4x0094 Unit
1
R/W
0 = m3/h = default
1 = m3/s
2 = l/s
uint16_t
4x0764
Modbus address
1
R
1 ≤ VAL ≤ 247
uint16_t
Flow (Differential pressure sensor 2)
Modbus Settings
see config #4x0067
see config #4x0067
see config #4x0067
see config #4x0067
Flow (Differential pressure sensor 1)
Differential pressure sensor 2
see config #4x0037
see config #4x0037
Analog input 2
Analog output 2