A-8. CL-208-E DCON Command Sets
- 123 -
Command
Description
@AABE
Read enable/disable beep on alarm
response
!AAHH, HH in hex, bit 0 for channel 0, bit 1 for channel 1,
etc, for each bit, 0: disabled, 1: enabled
@AABEHH
Enable/disable beep on alarm
HH in hex, , bit 0 for channel 0, bit 1 for channel 1, etc, for each bit,
0: disabled, 1: enabled
@AACH
Clear all high latched analog inputs to the current values
@AACHN
Clear channel high latched analog input to the current value, N = 0
for TVOC, 1 for relative humidity, 2 for temperature in 0.01°C, 3 for
temperature in 0.01°F, 4 for dew point temperature in 0.01°C, 5 for
dew point temperature in 0.01°F
@AACHCN
Clear high latched alarm of a channel, N = 0 for TVOC, 1 for relative
humidity, 2 for temperature in 0.01°C, 3 for temperature in 0.01°F, 4
for dew point temperature in 0.01°C, 5 for dew point temperature in
0.01°F
@AACL
Clear all low latched analog inputs to the current values
@AACLN
Clear channel low latched analog input to the current value, N = 0
for TVOC, 1 for relative humidity, 2 for temperature in 0.01°C, 3 for
temperature in 0.01°F, 4 for dew point temperature in 0.01°C, 5 for
dew point temperature in 0.01°F
@AACLCN
Clear low latched alarm of a channel, N = 1 for relative humidity, 2
for temperature in 0.01°C, 3 for temperature in 0.01°F, 4 for dew
point temperature in 0.01°C, 5 for dew point temperature in 0.01°F
@AADACN
Disable AI alarm of a channel, N = 0 for TVOC 1 for relative
humidity, 2 for temperature in 0.01°C, 3 for temperature in 0.01°F, 4
for dew point temperature in 0.01°C, 5 for dew point temperature in
0.01°F
@AADI
read DO
response
!AA00O00
@AADLB
Read the beginning of the period setting of the data logger for
period logging mode
response
!AAyyyymmddhhmmss,