C-11. CL-212 / CL-212-E Modbus Address Mappings (Base 1)
- 209 -
Address Description
Attribute
30545 ~
30551
40545 ~
40551
Low latched analog input value of channel 0 to 6
channel 0: CO
2
in 1ppm,
channel 1: PM2.5 in 1ug/m
3
,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4: temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R
30556
40556
Module reset status, 1: power-on, 2: watchdog, 3: software reset
command
Only for Modbus TCP protocol
R
40558
Ethernet host watchdog timeout value, 5 to 65535, in second, 0 to
disable.
Only for Modbus TCP protocol
R/W
30559
40559
Ethernet host watchdog timeout count.
Only for Modbus TCP protocol
R
30560
40560
Module name, 0x0213
Only for Modbus TCP protocol
R
40564
TCP disconnection timeout value, 5 to 65535, in second, 0 to
disable.
Only for Modbus TCP protocol
R/W
40565
Module reset timeout value, 30 to 65535, in second, 0 to disable.
Only for Modbus TCP protocol
R/W
40865
RTC year, 2000 to 2159
R/W
40866
RTC month, 1 to 12
R/W
40867
RTC date, 1 to 31
R/W
40868
RTC hour, 0 to 23
R/W
40869
RTC minute, 0 to 59
R/W
40870
RTC second, 0 to 59
R/W
40871
Total number of log records, low word
R
40872
Total number of log records, high word
R
40873
The starting record to read log data, low word
R/W
40874
The starting record to read log data, high word
R/W
40875
The status of the data logging, 0: stopped, 1: running
R
40876
The data logger command, 0: stop, 1: run, 2: run in period mode
R/W
40877
Continue writing when data logger is full, 0: no, 1: yes
R/W
40878
Hour of the data logger sampling period, 0 to 24
R/W