I-7242D user manual
I-7242D DeviceNet/Modbus RTU Gateway User’s Manual, July 2006, Version 1.1 40/124
0x09
Expected packet rate UINT
Get/Set
0x09c4
0x0C
Watchdog timeout action
USINT
Get/Set
0x01
0x0D
Produced connection path length
UINT
Get/Set
0x00
0x0E
Produced connection path
EPATH Get/Set (empty
path)
0x0F
Consumed connection path length
UINT
Get/Set
0x00
0x10
Consumed connection path
EPATH Get/Set (empty
path)
0x11
Production inhibit time
UINT
Get/Set
0x00
Instance (0x02) Attribute: Polled Command/Response Connection
Attribute ID
Attribute Name
Data Type Method
Value
0x01
State
USINT
Get
0x00 to 0x04
0x02 Instance
type USINT
Get
0x01
0x03
Transport class trigger
BYTE
Get/Set
0x82
0x04
Produced connection id
UINT
Get/Set
Table 3-2
0x05
Consumed connection id
UINT
Get/Set
Table 3-2
0x06
Initial comm. characteristics
BYTE
Get/Set
0x01
0x07
Produced connection size
UINT
Get/Set
(size of the input data)
0x08 Consumed
connection
size UINT
Get/Set
(size of the output data)
0x09
Expected packet rate
UINT
Get/Set
0x00
0x0C
Watchdog timeout action
USINT
Get/Set
0x00
0x0D
Produced connection path length
UINT
Get/Set
0x06
0x0E
Produced connection path EPATH
Get/Set
(area
path)
0x0F
Consumed connection path length
UINT
Get/Set
0x06
0x10
Consumed connection path EPATH
Get/Set
(area
path)
0x11
Production inhibit time
UINT
Get/Set
0x00
Instance (0x03) Attribute: Bit-Strobed Command/Response Connection
Attribute ID
Attribute Name
Data Type Method
Value
0x01
State
USINT
Get
0x00 to 0x04
0x02 Instance
type USINT
Get
0x01
0x03
Transport class trigger
BYTE
Get/Set
0x83
0x04
Produced connection id
UINT
Get/Set
Table 3-2
0x05
Consumed connection id
UINT
Get/Set
Table 3-2
0x06
Initial comm. characteristics
BYTE
Get/Set
0x02
0x07
Produced connection size
UINT
Get/Set
(size of the input data)
0x08 Consumed
connection
size UINT
Get/Set
0x08
0x09
Expected packet rate
UINT
Get/Set
0x00