MSD-501/502 Command Guide
76
@GEC / @SEC
Control command (CEC control)
Function
Getting
Setting
Format
@GEC, no
@SEC, no, delay, port, memo, error,
ch_1, cec_1 (, ch_2, cec_2
・・・
)
Return value
@GEC, no, delay, port, memo, error,
ch_1, cec_1 (, ch_2, cec_2
・・・
)
@SEC, no, delay, port, memo, error,
ch_1, cec_1 (, ch_2, cec_2
・・・
)
Parameter
no: Control command number
1 to 32
delay: Delay time
0 = 0 second to 999999 = 999.999 seconds
port: CEC control
For 4096 = CEC control, the value is 4096.
memo:
Up to 14 characters of 20 to 7D except 2C (,) from ASCII codes.
error: Processing at no response from the device
0 = Stop processing, 1 = Continue processing
ch_1-4: Output connector
1 = OUT1A, 2 = OUT1B, 3 = OUT2A, 4=OUT2B
cec_1-4: Control command
0 = Not controlled, 1 = POWER OFF, 2 = POWER ON
For get commands, the control output connector and control command are separated
from each other by a comma.
For set commands, the control output connector and control command can be
specified. Up to 32 commands can be specified by separating them by a comma.
By sending target parameters, the other parameters will be set to Not controlled
automatically.
Example
@GEC,7
@GEC,7,0,4096,DISPLAY1 ON,
0,1,2
Getting settings of control command 7.
・
Delay time: 0ms
・
Memo: DISPLAY1 ON
・
Error: Stop
・
OUT1 sink device: Turning on
・
Other outputs: not controlled.
@SEC,7,0,4096,DISPLAY1 ON,
0,1,2
@SEC,7,0,4096,DISPLAY1 ON,
0,1,2
Setting control command 7 as follows:
・
Delay time: 0 ms.
・
Memo: DISPLAY1 ON
・
Error: Stop
・
OUT1 sink device: Turning on
・
Other outputs: not controlled.
Remarks
-