Chapter 7 Exclusive Functions for iS7 Inverter Control/Monitoring
7-10
(2) iS7 Inverter Operation Reference
PLC option can provide operation reference to an inverter.
▶
Common area of inverter
Referring to the parameters (exclusively for control) of inverter common area in the “App. 4-6, page 4,
Appendix,” the addresses of the common area of the inverter operation reference are as follows.
Common Area
Address
Function
Detailed Description
BIT0
0: Stop command 1: Run command
BIT1
0: Reverse operation
1: Forward operation
BIT2 0
Æ
1 : Fault Reset
0x0382
Inverter Run Command
BIT3
0
Æ
1 : Free-run to stop
1
Æ
0: Fault reset of Free-run to stop
▶
Special D registers of PLC for inverter control corresponding to APO60 ~ 67
Register
Use of the Register
Remark
D4454
Data to be inputted in the common area parameter
address set up by APO60 (PLC Wr Data1)
PLC
Option
Æ
Inverter(control)
D4455
Data to be inputted in the common area parameter
address set up by APO61 (PLC Wr Data2)
PLC
Option
Æ
Inverter(control)
D4456
Data to be inputted in the common area parameter
address set up by APO62 (PLC Wr Data3)
PLC
Option
Æ
Inverter(control)
D4457
Data to be inputted in the common area parameter
address set up by APO63 (PLC Wr Data4)
PLC
Option
Æ
Inverter(control)
D4458
Data to be inputted in the common area parameter
address set up by APO64 (PLC Wr Data5)
PLC
Option
Æ
Inverter(control)
D4459
Data to be inputted in the common area parameter
address set up by APO65 (PLC Wr Data6)
PLC
Option
Æ
Inverter(control)
D4460
Data to be inputted in the common area parameter
address set up by APO66 (PLC Wr Data7)
PLC
Option
Æ
Inverter(control)
D4461
Data to be inputted in the common area parameter
address set up by APO67 (PLC Wr Data8)
PLC
Option
Æ
Inverter(control)
▶
Application and exemplary program
1) 1) Set up the inverter parameters as shown below. In the APO60(PLC Wr Data1), enter the
“0382Hex” which is the address (page 4, “App. 4-6, Appendix) of the common area of the inverter
operation reference.
Code
Function Name
Set Value
DRV01
Cmd Frequency
11.52 Hz
DRV06 Cmd
Source
PLC
DRV07 Freq
Ref
Src Keypad-1
APO60
PLC Wr Data1
0382 Hex
2) APO60 (PLC Wr Data1) corresponds with D4454 which is the special register of the PLC option by 1:1
relation. Since the APO60 (PLC Wr Data1) is registered with the common area address (0382Hex) of the
inverter operation reference, a specific value inputted in the D4454 in ladder program, the value will be
the operation reference of the inverter.