.1.3.6.1.4.1.25728.5100.55.1.2.n
npOutGrpBackupStatus.n
Integer
READ
Input reservation status for outlets group, where n is the index of outlet
group 1 or 2.
Possible values:
0 - the outlet group is powered from the primary input
1 - the group of outlets is powered from the backup input
.1.3.6.1.4.1.25728.5100.55.1.3.n
npOutGrpManualRevert.n
Integer
READ/WRITE Manual return to the primary input, where n is the index of the outlet group 1
or 2.
Write “-1” to initialize the return of the outlet group to the primary input
.1.3.6.1.4.1.25728.5100.55.1.6.n
npOutGrpMemo.n
DisplayString
READ
Memo of the outlet group, where n is the index of the outlet group 1 or 2.
- for group 1 - “1 ... 4”
- for group 2 - “5 ... 8
.1.3.6.1.4.1.25728.5100.55.1.7.n
npOutGrpPrimaryIn.n
Integer
READ
Index of the primary input for the outlet group, where n is the index of the
outlet group 1 or 2
.1.3.6.1.4.1.25728.5100.55.1.8.n
npOutGrpEnableBackup.n
Integer
READ
Input reservation for outlet group, where n is the index of outlet group 1 or 2.
Possible values:
0 — off
1 — on
.1.3.6.1.4.1.25728.5100.55.1.9.n
npOutGrpEnableAutoRevert.n
Integer
READ
Auto-return of the outlet group to the primary input, where n is the index of
the outlet group 1 or 2.
Possible values :
0 — off
1 — on
IR module
.1.3.6.1.4.1.25728.7900.1.1.0
npIrPlayCmd
Integer
READ/WRITE To send an IR command, write the number of the IR command.
.1.3.6.1.4.1.25728.7900.1.2.0
npIrReset
Integer
READ/WRITE To reset IR-transceiver write «1».
After reset, indicate IR command and check IP status
.1.3.6.1.4.1.25728.7900.1.3.0
npIrStatus
Integer
READ
Status of IR-transceiver.
These statuses are available:
commandCompleted (0) - command completed. A team that does not
require any process to execute.
protocolError (1) - wrong command code, or command not accepted.
commandAccepted (2) - command accepted, execution started. After
the completion of the command, the status does not change, since
there can no longer be any failures in this process. Wait about 0.5
seconds before sending the next command.
errorUnknown (16) — unknown error.
errorBadNumber (17) — wong parameter of the command.
errorEmptyRecord (18) — the attempt to play an empty cell.
errorFlashChip (19) — crash or failure of the memory chip inside the
IRC-TRv2 IR expansion module.
errorTimeout (20) — no response from IRC-TRv2 expansion module.
errorExtBusBusy (21) — the external i2c bus is busy, it is not possible
to communicate with the IRC-TRv2 IR expansion module (for example,
if the bus is short-circuited)
1-wire smoke sensors
.1.3.6.1.4.1.25728.8200.1.1.1.n
npSmokeSensorN.n
Integer
READ
The index of the 1-Wire smoke sensor, where n — a number of a sensor,
the number from 1 to 4 inclusive
.1.3.6.1.4.1.25728.8200.1.1.2.n
npSmokeStatus.n
Integer
READ
The status of the 1-Wire smoke sensor, where n —a number of a sensor, th
:
e number from 1 to 4 inclusive
0 — Normal
1 — Alert
4 — StopOut
5 — Failure
.1.3.6.1.4.1.25728.8200.1.1.3.n
npSmokePower.n
Integer
READ/WRITE Power control of the 1-Wire smoke sensor, where n — number of the
sensor,
:
the number from 1 to 4 inclusive
0 — Off
1 — On