Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
145
PartnerNo
Parameter: PartnerNo
Declaration: INPUT
Data type:
INT
Range of
values:
0 / 1 ... 32000
Default:
0
Explanation: Subscriber number of the partner
The subscriber number of the partner with which the block communicates
must be specified..
•
With a process typical this is normally the subscriber number of the master
station or the application of the control center (e.g. ST7cc).
•
With an operator typical this is normally the subscriber number of a station.
Effects of the value 0 (zero) on various typical classes
•
Sending process typicals
(Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Dat12D_S, Dat256D_S)
With the value 0 the data is sent to all subscribers to which an ST7
connection is configured. In this case, the parameter "PartnerObjectNo" is
automatically sent with the value zero by the process typical.
If PartnerNo is not found in the administration (DB BasicData), an entry to
this effect is made in the diagnostics buffer (event ID B101). The CPU
does not change to STOP. The block is then no longer processed,
however, until the error in the programming has been corrected.
Notes
–
If the"PartnerObjectNo" is missing, there must be a list on the partner
CPU from which the missing object number can be recognized.
–
Use of the block in a node station
If the CPU of the node station maintains both connections to higher-
level subscribers as well as to lower-level stations, a data frame with
PartnerNo = 0 is transferred to all subscribers in the direction master
station and in the direction stations.