Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
179
Parameter: BCD_Format
Declaration: INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
TRUE
Explanation: Counted value output in BCD format
•
If the parameter is activated the received counted value is output as a
positive BCD value at the "CountedValueOutput_n" output.
•
If the parameter is deactivated the counted value is output as a positive 32-
bit integer value.
For the different value ranges of the two formats, see the parameter "Count-
edValueOutput_n".
If the maximum counted value that can be represented is exceeded, the
counted value starts again at 0 and counting continues in the positive numeric
range.
Note on Cnt04D_R
The parameter exists only one in the typical and it applies to all 4 counted
values together. It is not possible to make an individual setting per counted
value. When using this parameter, per typical only counted values with an
identical output format should be output.
Parameter: CntValInvalid
Declaration: OUTPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Output
Q 0.0 ... Q n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7