Document #10-32813 Rev A; June 07, 2019
Page
47
of 69
Notes
l
Read-only files cannot be written via TFTP
l
Binary image transfer mode [-i] is recommended to prevent data loss in some strings
Command Format using Windows® 7 native TFTP client
TFTP [-i] host [GET | PUT] source [destination]
Sample Read
Read the Modbus® TCP configuration file (ModbusTcp.csv) from the NOR FLASH drive and place it in a folder in the
temporary directory.
TFTP -i rma-1894854 GET nor:\Gateway\ModbusTcp.csv %TEMP%\TFTP\ModbusTcp.csv
Sample Write
Write the Modbus® TCP configuration file (ModbusTcp.csv) from a folder in the temporary directory to the NOR FLASH
drive.
TFTP -i rma-1894854 PUT %TEMP%\TFTP\ModbusTcp.csv nor:\Gateway\ModbusTcp.csv
SNTP Client
Key
Value
Feature Definition
SntpAddress 216.239.35.4
SNTP Cli-
ent
Ethernet IPV4 address of a SNTP server as a string. This record is not a member of
the default file, and therefore, the feature is disabled. If you wish to use this feature,
you must add this record to the setup file.
SNTP Address
The RMA PLUS implements a Simple Network Time Protocol (SNTP) client. If the configuration key SntpAddress is
present, the RMA PLUS will attempt to synchronize its time with the configured SNTP server once per day. If the con-
nection fails, the RMA PLUS will try again at a faster interval until the connection is successful.
Wireshark
Wireshark is an Ethernet network analyzer. If you are trying to diagnose an Ethernet issue, Wireshark is an invaluable
tool. The factory may ask for a network capture to help diagnose problems.
If the problem is between PC software and the RMA PLUS, you can install Wireshark on the PC with no additional con-
figuration. If the problem is between a device without Wireshark and the RMA PLUS, you can activate the port mirroring
feature of the embedded switch to obtain a network capture.
Ethernet Members in RMA PLUS
Ethernet 70 (0x46), Instance 2
Member ID Member Name
Data
Type
Access NV Min Max Default
Comments / Description
3
0x03 Modbus® TCP
Enable
ENUM16 RW
F
--
--
106
59: No; 106: Yes
4
0x04 Modbus® TCP
Word Order
ENUM16 RW
F
--
--
1331
1331: Low High; 1330: High Low
7
0x07 Watbus Enable
ENUM16 RW
F
--
--
106
59: No; 106: Yes
8
0x08 HTTP Server
ENUM16 RW
F
--
--
106
59: No; 106: Yes