Document #10-32813 Rev A; June 07, 2019
Page
38
of 69
Key
Value
Feature
Definition
LogIntervalSec
integer of 1-
86,400
5 by default
Data Logging
This applies to models RMAP-XX
D
X-XXXX. This key defines the data log
interval in seconds, entered as an integer with a range of 1 – 86,400
seconds. Any value outside this range is clipped.
Setup Key: LogIntervalSec
Key
Value
Feature Definition
LogKeepDays integer
1 - 365
10 by
default
Data log-
ging
This key only applies if the model number is RMAP-XX
D
X-XXXX.
This key defines the number of log files (days) to keep. It is interpreted as an integer with a range of 1 –
365 days. A value greater than 365 days will disable this feature. The default value is ten days.
Setup Key: LogKeepDays
The data logging configuration is user-defined. A sample file exists in the path defined by the DataLog key. Add records
to this file as necessary, keeping the following in mind:
l
A new file is created every day. Mount the MICRO SD drive to access / manage log files.
l
Maximum of 2000 valid records.
l
Maximum of 500 unique data points per standard bus and zone.
l
“(Z:C.M.I)” for standard and intermodule bus records where Z = Zone ID, C = Class ID, M = Member ID, I =
Instance ID
l
“(A:R.N)” for Modbus® records where A = Address, R = Register, N = Number of Registers
l
Headers are only appended once, when the file size equals zero.
l
The format column may be used to override the default numeric data format for the given record. Standard printf style
format strings may be used i.e. %f, %i, %X, etc. Leave this field empty to use the default data format.
l
The format of the log file name is “YYYY-MM-DD.csv.”
l
Files with a creation date older than LogKeepDays are deleted. Folders, read-only files, and hidden files are excluded.
l
File maintenance is triggered when a new file is created (file size is zero).
l
All
are supported.
l
Unsupported data types are blank. This may be observed in a log file if the RMA PLUS cannot read the data type of a
member. This will be the case if the target device is not present or the bus hasnot acquired the member attributes.
l
If the file nor:\Text.csv exists, enumerations will be logged as strings. If not, they will be logged as their integer equi-
valent.
l
Producer / consumer data points will display 99999 if an error exists.
Header
Format
Bus
Segment
Zone
Class
Instance
Member
Refresh Count
DEV 1 Hardware ID
1
0
0
1
1
1
0
TST 1 Tick
1
0
0
16
1
6
0
RTC 1 Timestamp
1
0
0
36
1
19
0
DataLog.csv default configuration