outputFailureMaxCurrent
of
outputSupervisionBehavior
before.
Item
Type
Access
Status bits / Switch functions
outputStatus bits
read
outputEnableKill (13)
outputEmergencyOff (14)
outputSwitch integer read-write
Off (0)
On (1)
resetEmergencyOff (2)
setEmergencyOff (3)
clearEvents (10)
DESCRIPTION
Read: An enumerated value which shows the current state of the output channel.
Write: Change the state of the channel.
If the channel is On, and the write value is Off, then the channel will switch off.
If the channel is Off, and the write value is On, and if no other signals (
mainInhibit, outputInhibit,
outputEmergencyOff or outputFailureMaxCurrent
) are active, then the channel will switch on.
If the write value is
resetEmergencyOff
, then the channel will leave the state
EmergencyOff
.
A write of
clearEvents
is necessary before the voltage can ramp up again.
If the write value is
setEmergencyOff
, then the channel will have the state
EmergencyOff
, which means
that the High Voltage will switch off without a ramp and reset of the
outputVoltage
to null volt.
If the write value is
clearEvents
, then all failure messages of the
outputStatus
will be reset (all channel
events, all module events and the state
EmergencyOff
.
Item
Type
Access
Switch functions
groupsSwitch.64 integer
write
Off (0),
On (1)
resetEmergencyOff (2)
setEmergencyOff (3),
disableKill (4)
enableKill (5)
clearEvents (10)
DESCRIPTION
Read: This function is not defined with groups of output channels.
Write: Switch the state of all channels of group 64 (all high voltage modules).
If any channel is On, and the write value is Off, then all channels will switch off. If any channel is Off, and
the write value is On, and if no other signals (
mainInhibit, outputInhibit, outputEmergencyOff or
outputFailureMaxCurrent
) are active, then all channels will switch on.
If the write value is
resetEmergencyOff
, then all channels will leave the state
EmergencyOff
.
A write of
clearEvents
is necessary before the voltage can ramp up again.
If the write value is s
etEmergencyOff
, then all channels will have the state
EmergencyOff
, which means
that the High Voltage will switch off without a ramp and reset of the
outputVoltage
to null volt.
If the write value is
disableKill
, then all channels will switch to
disableKill
.
If the write value is
enableKill
, then all channels will switch to
enableKill
.
If the write value is
clearEvents
, then all failure messages of the
outputStatus
will be reset (all channel
events, all module events and the state
EmergencyOff
).
Item
Type
Access
outputSupervisionBehavior integer read-write
DESCRIPTION
A bit field packed into an integer which define the behaviour of the output channel / power supply after
failures.