All other SNMP items from the branch
outputTable
are readable for the SNMP compatibility but will not
be used by the load unit.
7.6
ISEG Module commands
Item
Type
Access
moduleDescription
octet string
read
Reply:
Company name, firmware name, channel number, serial number
for instance iseg, E24D1, 24, 713100, 5.03
Item
Type
Access
moduleAuxiliaryMeasurementVoltage0
float
read
Returns the measurement value of the line supply 24 Volt.
moduleAuxiliaryMeasurementVoltage1
float
read
Returns the measurement value of the line supply 5 Volt.
7.7
WIENER MPV Module commands
outputUserConfig OBJECT-TYPE
-- FROM WIENER-CRATE-MIB
SYNTAX Integer32 (0..127)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Definition of user-changeable items.
A bit field packed into an integer which define the behavior of the output channel.
Usable for WIENER LV devices only.
The position of the bit fields in the integer value are:
Bit 0: Voltage ramping at switch off:
0: Ramp down at switch off.
1: No ramp at switch off (immediate off)
Bit 1, 2: Set different regulation modes, dependent on the
cable inductance:
0: fast: short cables, up to 1 meter.
1: moderate: cables from 1 to 30 meter.
2: fast: identical to 0 (should not be used)
3: slow: cables longer than 30 meter.
Bit 3: Internal sense line connection to the output (MPOD only):
0: The sense input at the sense connector is used
30. May 2018
41