Section 11. Programming Resource Library
117
appears on the screen as shown in
FIGURE. Entering SDI-12 Transparent Mode
(p. 117). Press <Enter> until the CR200(X) responds with the prompt
“CR200(X)>”. Type “SDI12” at the prompt (without the quotes) and press
<Enter>. An “Entering SDI12 Terminal” response indicates that SDI-12
Transparent Mode is active and ready to transmit SDI-12 commands and display
responses.
Figure 44: Entering SDI-12 Transparent Mode
11.4.2.2 SDI-12 Programmed Mode
Routine SDI-12 measurements require that issuance of commands and
interpretation of sensor responses be automated. Commands entered into the
SDIRecorder () instruction differ slightly in function from commands entered in
transparent mode. In transparent mode, for example, the operator manually
enters
aM!
and
aD0!
to initiate a measurement and get data, with the operator
providing the proper time delay between the request for the measurement and
the request for the data. In programmed mode, the CR200(X) provides
command and timing services within a single line of code. For example, when
the SDI12Recorder() instruction is programmed with the M! command (note
that SDI-12 address is a separate parameter), the CR200(X) issues the
aM!
AND
aD0!
commands with proper elapsed time between the two. The CR200(X)
automatically issues retries as well as other services designed to make the SDI-
12 measurement work as trouble free as possible.
TABLE. SDI-12Recorder ()
Commands
p. 118 summarizes CR200(X) actions triggered by some
SDI12Recorder commands.
Summary of Contents for CR200
Page 32: ...Section 2 Quickstart Tutorial 22 ...
Page 45: ...Section 3 Overview 35 3 3 Specifications ...
Page 46: ...Section 3 Overview 36 ...
Page 58: ...Section 4 Sensor Support 48 ...
Page 62: ...Section 5 Measurement and Control Peripherals 52 ...
Page 78: ...Section 8 CR200 X Configuration 68 ...
Page 102: ...Section 9 Programming 92 ...
Page 138: ...Section 11 Programming Resource Library 128 ...
Page 156: ...Section 16 Support Software 146 ...
Page 160: ...Section 17 Care and Maintenance 150 ...
Page 167: ...Section 18 Troubleshooting 157 18 3 3 2 Charging Circuit Test Solar Panel ...
Page 168: ...Section 18 Troubleshooting 158 18 3 3 3 Charging Circuit Test Transformer ...
Page 169: ...Section 18 Troubleshooting 159 18 3 3 4 Adjusting Charging Circuit Voltage ...
Page 170: ...Section 18 Troubleshooting 160 ...
Page 184: ...Appendix A Glossary 14 ...
Page 190: ...Appendix B Status Table and Settings 20 ...
Page 192: ...Appendix C Serial Port Pin Outs 22 ...
Page 211: ......