Device Profile Area
CAN-CBX-REL4
Manual • Doc.-No.: C.3012.21 / Rev. 1.1
Page 85 of 99
7.10.4 Error Mode Output 8-bit (6206
h
)
The error mode is evaluated if the module is switched into Stopped state.
This object and object 1029
h
together determine whether the relays are set to an error value in case of
an internal device error. The error value is specified in object 6207
h
,.
Index
Sub-
index
Description
Value range
Default
Data type
Access
6206
h
0
number_of_output_8-bit
1
1
unsigned 8
const
1
error_mode_output_8-bit
00...0F
h
0F
h
unsigned 8
rw
Assignment of the variable error_mode_output_8-bit:
This object determines whether the relays are set to an error value defined in object 6207
h
, in case of
an internal device failure.
Bit:
7
6
5
4
3
2
1
0
Relay:
-
-
-
-
Rel_4
Rel_3
Rel_2
Rel_1
Bit value Rel_x
Meaning
1
Relay state is set to the value predefined in object 6207
h
(default).
0
Relay state shall be kept if an error occurs.