KNX/EIB
KNX Gateway for IR
20
Fan speed control setting
——Parameter “Control value for fan speed auto/low/medium/high/auto”
These parameters are for setting the control values sent by each fan speed. According to object
datatype, the range of control value:
0..255 / 0..100
——Parameter “Status value for fan speed auto/low/medium/high/auto”
These parameters are for setting the status feedback values of each fan speed. According to
object datatype, the range of control value:
0..255 / 0..100
Parameter “Swing control”
This parameter is for setting whether to enable swing control. When enabled, relevant settings are
visible. Options:
Disable
Enable
Mode control function
Parameter “Auto/Heating/Cooling/Fan/Dehumidification mode”
These parameters are for setting whether to enable each Air-condition mode. When enabled,
relevant settings are visible.
——Parameter “Control value for heating/cooling/dehumidification/fan/auto mode [0..255]”
These parameters are visible when modes enabled. Set to switch to each mode control value.
Options:
0..255
——Parameter “Status value for heating/cooling/dehumidification/fan/auto mode [0..255]”
These parameters are visible when modes enabled and “AC status response object” enabled. Set
to the each mode status feedback value. Options:
0..255
The following is mainly explain IR code number assignment of various combination control
functions. In Air-condition control system, usually a IR code includes multiple control instructions, such
as setpoint temperature, modes, fan speed, swing and etc. Therefore, it need configure IR code
according to actual study when assign IR code for each combination control function in ETS. The study
of IR code and related configuration can be edited or checked in configuration software tool or DCA, as
following figure.