Using the PRO3X Command Line Interface (CLI)
PRO3X User Guide
–
Command Line Interface (CLI)
106 of 182
Example - Inlet Naming
The following command assigns the name "AC source" to the inlet 1. If your PRO3X contains multiple inlets, this command
names the 1st inlet.
config:#
inlet 1 name "AC source"
Overcurrent Protector Configuration Commands
An overcurrent protector configuration command begins with
ocp.
The command configures an individual circuit breaker or
fuse which protects outlets.
Changing the Overcurrent Protector Name
This command names a circuit breaker or a fuse which protects outlets on your PRO3X.
config:#
ocp <n> name "<name>"
Variables:
<n> is the number of the overcurrent protector that you want to configure. The value is an integer between 1 and 50.
<name> is a string comprising up to 64 ASCII printable characters. The <name> variable must be enclosed in quotes when it
contains spaces.
Example - OCP Naming
The command assigns the name "Email servers CB" to the overcurrent protector labeled 2.
config:#
ocp 2 name "Email servers CB"
User Configuration Commands
Most user configuration commands begin with
user
except for the password change command.