RD4 CANopen®
100D-00 Life Time Factor
[Unsigned8, rw]
Default = 0
“Node guarding protocol” controlled by Master. For further details see section
“8.4 Node guarding protocol” on page 68.
1010-01 Save Parameters
[Unsigned32, rw]
Use this object to save all parameters on non-volatile memory.
Write
save
(ASCII code in hexadecimal form) in the data bytes:
Master
Slave
COB-ID
Cmd
Index
Sub
Data bytes
600+ID
23
10
10
01
73
61
76
65
Slave
Master (confirmation)
COB-ID
Cmd
Index
Sub
Data bytes
580+ID
60
10
10
01
00
00
00
00
1011-01 Restore Default Parameters
[Unsigned32, rw]
This object allows you to restore all parameters to default values (they are set at
the factory by Lika Electronic engineers to allow the operator to run the device
for standard operation in a safe mode).
Write
load
(ASCII code in hexadecimal form) in the data bytes and then issue a
Reset node
command:
Master
Slave
COB-ID
Cmd
Index
Sub
Data bytes
600+ID
23
11
10
01
6C
6F
61
64
Slave
Master (confirmation)
COB-ID
Cmd
Index
Sub
Data bytes
580+ID
60
11
10
01
00
00
00
00
Master
Slave (reset node)
COB-ID
Cmd
Slave ID
000
81
ID
MAN RD4 CB E 1.5
Programming parameters
48 of 72