alarm_low_lower1 - alarm_low_lower4
A warning is triggered, if the measurement value drops to or below this value.
alarm_low_upper1 - alarm_low_upper4
A warning is triggered, if the measurement value meets or exceeds this value.
alarm_high_lower1 alarm_high_lower4
An alarm is triggered, if the measurement value drops to or below this value.
alarm_high_upper1 - alarm_high_upper4
An alarm is triggered, if the measurement value meets or exceeds this value.
hyst1 - hyst4
Hysteresis for the all-clear in the event of an alarm/warning (e.g. Hyst=5%, alarm or warning at
100 -> all-clear at 95) or reset the trigger (e.g. Hyst=5%, level = greater or equal, trigger at 100 ->
reset at 95)
trigger_value1 - trigger_value4
Levels for initiating the trigger. The hysteresis from the "Alarm" tab is used to determine the
level to reset the trigger.(not for universal inputs in "Digital" mode)
trig_alarm_lo1 - trig_alarm_lo4
1)
A "high" at the universal input triggers a "warning". (only for universal inputs in "Digital"
mode)
trig_alarm_hi1 - trig_alarm_hi4
1)
A "high" at the universal input triggers an "alarm". (only for universal inputs in "Digital"
mode)
trig_fault_lo1 - trig_fault_lo4
1)
A "high" at the universal input triggers a "fault warning". (only for universal inputs in "Digital"
mode)
trig_fault_hi1 - trig_fault_hi4
1)
A "high" at the universal input triggers a "fault alarm". (only for universal inputs in "Digital"
mode)
trig_meas_quick1 - trig_meas_quick4
1)
The "Record interval on event" should be used.
trig_xmit_start1 - trig_xmit_start4
1)
Initiate transmission
trig_undershoot1 - trig_undershoot4
Selection to determine whether the measurement value must be greater/equal or less/equal to
the trigger level to initiate the trigger (not for universal inputs in "Digital" mode)
Value
Explanation
0
Greater or equal
1
Less or equal
trig_trans_quick1 - trig_trans_quick4
1)
The "Transmission cycle quick" should be used.