i)
CmdABVOnStopOff
Command to configure the Automatic Bypass Valve (ABV) to remain closed
when either the STOP KEY is pressed or a CmdStop is received. A “1” will
be returned if the command is successfully carried out.
ii)
CmdABVOnStopOn
Command to configure the Automatic Bypass Valve (ABV) to open
automatically when either the STOP KEY is pressed or a CmdStop is
received. A “1” will be returned if the command is successfully carried out.
iii)
CmdCloseABV
Command to CLOSE the Automatic Bypass Valve (ABV). A “1” will be
returned if the command is successfully carried out, and a “0” will be
returned if an ABV is NOT FITTED or the ABV is open as the result of a
fault event.
iv)
CmdEnergyReset
Command to reset the elapsed energy savings data. A “1” will be returned
if the command is successfully carried out.
v)
CmdOpenABV.
ommand to OPEN the Automatic Bypass Valve (ABV). A “1” will be
returned if the command is successfully carried out, and a “0” will be
returned if an ABV is NOT FITTED or the ABV is open as the result of a
fault event.
vi)
CmdReset
This command is equivalent to the RESET KEY being pressed on the
dryer’s Control Panel; all fault events, which are not still active, will be
reset. A “1” will be returned if the command is successfully carried out.
vii)
CmdStart
This commands the dryer connected to the network node to START cycling
(it is equivalent to the START KEY being pressed on the dryer Control
Panel). A “1” will be returned if the command is successfully carried out.
viii)
CmdStop
This commands the dryer connected to the network node to STOP cycling,
and enter STANDBY (it is equivalent to the STOP KEY being pressed on
the dryer Control Panel). A “1” will be returned if the command is success
fully carried out.