Appendix 1 list of Parameters
State 16.11.15
Misprints and technical changes reserved
Page 20
15: Communication
ID
Name
Value-Range
Default-Value
Unit
Access
612 Profibus Status word
0000h ... 07FFh
---
[bits]
R
Display of Profibus status word.
Bit Name
Note
0 BusStReadyToSwitchON
Electronic voltage available
1 BusStReadyToSwitchOperate
Intermediate circuit loaded
2 BusStDriveEnabled
End stage enabled
3 BusStError
0 = No fault
4 BusStNo_AUS2
Not supported
5 BusStNo_AUS3
Not supported
6 BusStStartUpLockOut
End stage blocked C4 or C6
7 BusStWarning
0 = No warning
8 BusStSpeedToleranceRange
Within tolerance range
9 BusStControlledThroughProfibus
Profibus active
10 BusStnReached
0 = Actual rotational speed different from setpoint
speed
11
12
13
14
15
15: Communication
ID
Name
Value-Range
Default-Value
Unit
Access
613 Profibus configuration
0000h ... FFFFh
---
[bits]
R
Display of current baudrate and PPO type.
Bit Name
Note
0 12 MBaud
1 6 MBaud
2 3 MBaud
3 1,5 MBaud
4 500 KBaud
5 187,5 KBaud
6 93,75 KBaud
7 45,45 KBaud
8 19,2 KBaud
9 9,6 KBaud
10 PPO-Overrun
PPO content larger than selected PPO type
11 PPO-Typ1
12 PPO-Typ2
13 PPO-Typ3
14 PPO-Typ4
15 PPO-Typ5
Baudrate and PPO types will be transmitted by Profibus master on initialisation!
15: Communication
ID
Name
Value-Range
Default-Value
Unit
Access
618 FBus Speed Decimals
-1 ... 3
0
RW
619 FBus Current Decimals
-1 ... 3
1
RW
620 Tx PDO 1
-1 ... 3000
0
RW
621 Tx PDO 2
-1 ... 3000
0
RW
622 Tx PDO 3
-1 ... 3000
0
RW