WAGO-I/O-SYSTEM 750
Fieldbus Communication 279
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Instance 2 – Port 2
Table 217: Ethernet link (F6
hex
) – Instance 2
Attribute ID Access Name
Data type Description
Default value
1 Get
Interface
Speed
UDINT
Transfer rate
10 (0x0000000A) or
100 (0x00000064)
2 Get
Interface
Flags
DWORD
Interface
configuration
and status information
Bit 0: Link status
Bit 1: Half/full lduplex
Bit 2…4: Detection
status
Bit 5: Manual settings
require reset
Bit 6: Local hardware
error
Bit 7…31: Reserved
Value is dependent
upon Ethernet
connection.
3 Get
Physical
Address
ARRAY
of 6
UINTs
MAC layer address
MAC-ID des
Fieldbus couplers/
controllers
Interface Control STRUCT
of:
Configuration of the
physical interface
-
Control Bits
WORD
Interface configuration
bits
Bit 0: Automatic
detection
Bit 1: Default duplex
mode
Bit 2…15: Reserved
0x0001
6 Set
Forced Interface
Speed
UINT
Preset interface speed 10 (0x000A) or
100 (0x0064)
7 Get
Interface
Type
USINT
Interface
type
Value 0: Unknown
Value 1: Internal
interface; e.g., in the
case of an integrated
switch
Value 2: Twisted pair
(e.g. 100Base-TX).
Value 3: fiber glass
(e.g. 100Base-FX).
Value 4…256:
Reserved
2 (0x02) – Twisted
Pair
8 Get
Interface
Status
USINT
Interface
status
Value 0: Unknown
Value 1: Interface
active and ready to
send/receive.
Value 2: Interface
deactivated.
Value 3: Interface is
testing
Wert 4…256:
Reserved
-