User Manual DEV 5072
54
Copyright DEV Systemtechnik GmbH 2016-2017
5.5.4.3.5.2
.application.channelTable.channelEntry.channelOn
OID:
.1.3.6.1.4.1.21035.34.2.5.1.2
.x
Syntax:
INTEGER {off (1), on (2), notApplicable (3)}
Access:
read-write
Description:
The power supply module operation status can be read or set,
possible values:
"
1
" off:
the power supply module is (to be) deactivated
"
2
" on:
the power supply module is (to be) activated
"
3
" not applicable: the module is not present, thus the operation
status cannot be obtained or changed
5.5.4.3.5.3
.application.channelTable.channelEntry.channelAcInputStatus
OID:
.1.3.6.1.4.1.21035.34.2.5.1.3
.x
Syntax:
INTEGER {ok (1), warning (2), error (3), notApplicable (4)}
Access:
read-only
Description:
The status of the related AC line, possible values:
"
1
" ok:
the AC input voltage is within specifications
"
2
" warning: the AC input voltage is <102 V AC (i.e. limited
output performance)
"
3
" error:
the AC input voltage exceeds the specifications
"
4
" not applicable: the power supply module is not present, thus
the AC input status cannot be obtained
5.5.4.3.5.4
.application.channelTable.channelEntry.channelTempWarning
OID:
.1.3.6.1.4.1.21035.34.2.5.1.4
.x
Syntax:
INTEGER {ok (1), warning (2), error (3), notApplicable (4)}
Access:
read-only
Description:
The temperature status of the power supply module,
possible values:
"
1
" ok:
the temperature is within specifications
"
2
" warning: the temperature is ~10° C below the safe limit
"
3
" error:
the temperature is higher than the safe limit
"
4
" not applicable: the power supply module is not present, thus
the temperature status cannot be obtained
5.5.4.3.5.5
.application.channelTable.channelEntry.channelFanStatus
OID:
.1.3.6.1.4.1.21035.34.2.5.1.5
.x
Syntax:
INTEGER {ok (1), error (3), notApplicable (4)}
Access:
read-only
Description:
The status of the power supply module fans, possible values:
"
1
" ok:
the fan status is ok
"
3
" error:
one or both fans are not working
"
4
" not applicable: the power supply module is not present, thus
the fan status cannot be obtained