User Manual DEV 5072
Copyright DEV Systemtechnik GmbH 2016-2017
55
5.5.4.3.5.6
.application.channelTable.channelEntry.channelOutVoltageSet
OID:
.1.3.6.1.4.1.21035.34.2.5.1.6
.x
Syntax:
INTEGER32
Access:
read-write
Description:
The output voltage setpoint of the module in [mV]
Note:
.channelOutVoltageSet is defined as read-write due to downward compatibility
reasons with the DEV 5071, but for the DEV 5072 it can be read only.
If the power supply module slot is empty, "
9999
" is returned. Otherwise the
value of the output voltage setpoint of the device (.outputVoltageSet, please
refer to chapter 5.5.4.3.6) is returned.
5.5.4.3.5.7
.application.channelTable.channelEntry.channelOutVoltage
OID:
.1.3.6.1.4.1.21035.34.2.5.1.7
.x
Syntax:
INTEGER32
Access:
read-only
Description:
The measured output voltage of the module in [mV]
"
9999
" is returned if the power supply module slot is empty.
5.5.4.3.5.8
.application.channelTable.channelEntry.channelOutCurrentSet
OID:
.1.3.6.1.4.1.21035.34.2.5.1.8
.x
Syntax:
INTEGER32
Access:
read-write
Description:
The current alarm level of the power supply module in [mA]
Note:
.channelOutCurrentSet is defined as read-write due to downward compatibility
reasons with the DEV 5071, but for the DEV 5072 it can be read only.
If the power supply module slot is empty, "
9999
" is returned. Otherwise e.g.
"
49400
" (i.e. 49.4 A) is returned which corresponds to ~95% of the current
capability of a 48 V power supply module. For this reason, it is recommended
to use .outputCurrentLim (please refer to chapter 5.5.4.3.7) for the current
alarm level of the device, instead.
5.5.4.3.5.9
.application.channelTable.channelEntry.channelOutCurrent
OID:
.1.3.6.1.4.1.21035.34.2.5.1.9
.x
Syntax:
INTEGER32
Access:
read-only
Description:
The measured output current of the module in [mA]
"
9999
" is returned if the power supply module slot is empty.