background image

DEFROST CONTROL

The instrument can be used to select dif-
ferent types of defrosting with the para-
meter 

dty, defrost type

(defrost execution mode). 

The dty parameter can have these values: 
0 = Electrical or Off Cycle defrost 
(Compressor OFF during Defrost);
1 = Reverse cycle defrost 
(hot gas - Compressor On during Defrost);
2 = ’Free’ : Independent defrost 
(compressor cycles ON/OFF according to
temperature during defrost)

Configuration of 3

rd

probe as 2nd evap-

orator probe

The 3

a

probe can be used to control the

defrosting of a second evaporator by con-
figuring a relay output as a 2nd evaporator
defrost relay (see par. H21…H26). 
To implement this function: 
a) configure the 3

rd

probe in 2nd evapora-

tor defrost control mode (par. H43=2EP). 
b) configure a relay output as 2nd evapo-
rator defrost relay (configuration parame-
ters H21…H26). 
c) define the defrost mode by setting
parameter H45.

Start of defrosting

If two evaporators are used, defrosting
starts in three different ways that are
determined by parameter H45.
• H45=0:  Defrosting is enabled by con-
trolling the temperature of the 1st evapo-
rator so it is lower than parameter dSt,
•H45=1: Defrosting is enabled by control-
ling so that at least one of the two probes
is below its end of defrosting temperature
(dSt for the 1st evaporator and dS2 for
the 2nd evaporator)
• H45=2: Defrosting is enabled by control-
ling so that both the probes are below
their respective end of defrosting set
points (dSt for the 1st evaporator and dS2
for the 2nd evaporator) 
The probe error condition is considered
the defrost calling probe. 
When defrosting is terminated by a probe
or is timed out (see par. dEt), dripping fol-
lows (see par. dt).

End of defrosting

If two evaporators are used, defrosting
ends when both the probes have reached
or exceeded their respective end of
defrosting set points (dSt for the 1st evap-
orator and dS2 for the 2nd evaporator) 
If one or both the probes are faulty,
defrosting is ended by a time-out.

NOTE:

• If there are no conditions for defrosting,
the request is ignored. 
Defrosting of a single evaporator ends
when the value read by the respective
probe is equal to or higher than the end
of defrosting temperature or a time-out
occurs. Dripping starts when both defrosts
have been completed.

• If one or both the probes are faulty,
defrosting in the corresponding evaporator
is ended by a time-out. 
The start of defrosting is permitted when
the corresponding temperature is lower
than the corresponding set point (dSt or
dS2).
• If probe 3 is not configured as a probe
on the second evaporator (H43

2),

defrosting on the second evaporator
occurs if a digital output is configured to
control defrosting on the second evapora-
tor (see par. H21..H25). If this is the case,
defrosting is confirmed (as if ST3<dS2)
and ends with a time-out. The fan con-
troller remains unchanged.

GENERAL PRESSURE SWITCH  INPUT
CONTROLLER

This controller performs diagnostics on an
associated digital input using a configura-
tion table. It is activated by setting para-
meters H11 and H12 = 9. 
If the pressure switch input trips, the com-
pressor loads are immediately deactivated,
the alarm LED lights up to signal tripping
and the label nPA in the alarm folder
appears on the display. 
Controlling is performed using 2 parame-
ters PEn and PEI: 

nPA is a subfolder of AL (Alarms), and
keeps a record of each time the pressure
switch is activated if the value indicated by
PEn is reached in a period of time that is
less than or equal to PEI, the label nPA is
replaced by PA (pressure alarm). 
The alarm conditions only occurs when the
maximum number of alarms is reached
before the time indicated by parameter
PEI expires. As soon as the first alarm
occurs, the time PEI is calculated. 
If the number of times the pressure switch
is activated exceeds the number estab-
lished PEn in the period PEI:
- compressor outputs, fans and defrosting
are deactivated
- the label PA is displayed in the subfolder
nPA
- the alarm LEDs and alarm relay if config-
ured are switched on.

NOTE: 

Once the device is in alarm mode,

it must be switched off and on again or
reset by activating the rAP parameter in
the functions menu. The nPA folders can
be reset using the rPA function in the Fnc
folder.

NOTE: 

If parameter PEn is set to 0 the

function is excluded and the alarms and
counts are disabled.

CONDENSER FAN CONTROLLER

This controller is associated with probe
Pb3 and features:
- operating set point
- operating differential
- exclusion of fans in defrosting mode
- start-up delay after end of defrosting If a
digital output is set as condenser fans
(H21...H24=10) the output will behave as
shown below: 

If probe Pb3 is not present and alarm E3 is
active, the controller will always be on
during the defrost cycle. 
Probe 3 can be excluded and the failed
connection with the instrument will not
trigger an error message.

NOTE: 

During dripping time the output is

OFF.

NOTE: 

If a digital output is programmed

as condenser fans (H21...H25 =10) parame-
ter SA3 is always an absolute value irre-
spective of the value of parameter Att.

DIAGNOSTICS

The alarm condition is always signalled by
a buzzer (if present) and the alarm icon
LED. The alarms from the faulty thermo-
stat control probe (probe 1), the faulty
evaporator probe (probe 2), and the faulty
display probe (probe 3) appear directly on
the instrument display as E1, E2, and E3
respectively. 

An error condition in probe 1 (thermostat
control) causes the following:
• E1 code appears on display
• compressor is activated as indicated by
“Ont” and “Oft” parameters if these are
programmed for duty cycle or: 

The error condition for probe 2 (evapora-
tor) causes the following:
• E2 code appears on display
• end of defrost due to time-out.

The error condition for probe 3 (display)
causes the following:
• E3 code appears on display Other alarms
do not appear on the instrument display

ID 985/S/E/CK - ID985/E LX

4/14

Par.

Description

PEn

number of errors allowed per maximum/

minimum pressure switch input switch

input (number) 

PEI

Minimum/maximum pressure switch error

count time (minutes)

Output Value

Pb3 Value

ON

SCF OFF

SCF - dCF

DISPLAY

E1 
E2
E3

If simultaneous, they will be showed on the display
alternately every 2 seconds

FAULT

Faulty probe 1 (thermostat control)
Faulty probe 2 (1st evaporator)
Faulty probe 3 (display or 2nd evap-
orator)

Table of faulty probes

Ont


0
>0
>0

Oft

0
>0 
0
>0

Compressor output

OFF 
OFF 
ON 
dc

Summary of Contents for ID 985

Page 1: ...t point is entered set point ON for setting set point Compressor or relay 1 ON for compressor on blinking for protection delay or enabling blocked Defrosting ON when defrosting in progress blinking when activated manually or by digital input Alarm ON for active alarm blinking for silenced alarm Fans ON when fan is on aux ON when auxiliary output is operating aux fnc set ID985 E LX aux set fnc UP b...

Page 2: ...ed if it is not successful n will be displayed Download from reset Connect the copy card when the instrument is OFF The program ming parameters are downloaded when the device is switched on At the end of the lamp test the following messages are dis played for about 5 seconds dLY label if copy operation is successful DLn label if operation fails NOTE after the parameters have been downloaded the de...

Page 3: ...hen it is on stand by according to the following parameters The Stand by controller can be digital input or button enabled if suitably configured The status of the instrument when on stand by is determined by the value of parameter H08 Three possible operating modes are defined EXAMPLE 1 the display is off and the con trollers active the instrument signals any alarms by reactivating the display OF...

Page 4: ...r loads are immediately deactivated the alarm LED lights up to signal tripping and the label nPA in the alarm folder appears on the display Controlling is performed using 2 parame ters PEn and PEI nPA is a subfolder of AL Alarms and keeps a record of each time the pressure switch is activated if the value indicated by PEn is reached in a period of time that is less than or equal to PEI the label n...

Page 5: ...so signalled for address ing conflicts when a the number of Slaves set on the MAS TER is different from the actual number of Slaves on the network b 2 or more Slaves have the same address ELECTRICAL CONNECTIONS Warning Always switch off machine before working on electrical connections The instrument has screw terminals for connecting electrical cables with a maxi mum diameter of 2 5 mm2 only one c...

Page 6: ... or after a power failure Not active if 0 0 250 0 1 2 min dty Defrost type 0 Electrical or Off Cycle defrost Compressor OFF during Defrost 1 Reverse cycle defrost hot gas Compressor On during Defrost 2 Free Independent defrost compressor cycles ON OFF according to temperature during defrost 0 1 2 0 1 2 flag dit Period of time elapsing between the start of two defrosts 0 function disabled 0 250 6 1...

Page 7: ...y all the level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differential see FSt Fot 1 0 50 0 2 0 1 2 C F Fdt Delay before fan activation after defrosting 0 250 0 1 2 min dt Dripping time 0 250 0 1 2 min FCO Disables fans with compressor off Off y fans activ...

Page 8: ...f disabling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values or as a differential related to the set point 0 absolute value 1 value related to set point 0 1 0 2 flag AFd Alarm differential 1 0 50 0 2 0 1 2 C F HAL 4 Maximum alarm Temperature limit whose...

Page 9: ...lag L04 Refers to Slave only Distributed display n Slave displays local values y Slave displays Master display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of remote functions from Master y accepts activation of remote functions from Master n y n 2 Flag L0...

Page 10: ...d by operating mode 0 only display switched off 1 display on and controls locked 2 display off and controls locked 0 1 2 2 2 num H12 6 Configuration of digital inputs polarity Same as H11 9 9 0 2 num Configuration CnF label H02 Quick activation time for functions with configured buttons Not possible for aux time expected 1 second 0 15 5 2 sec H06 Button input aux door switch light active when inst...

Page 11: ...eter 1 2 1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOTES 1 See Duty Cycle page 4 3 If relative values are present par Att 1 parameter HAL is set to positive values and the parameter LAL is set to negative values LAL 4 Refers exclusively to high a...

Page 12: ...oduced by the probe is added to any error that is characteristic of the instrument RS485 RS485 Personal Computer PCI1110 1120 TelevisCompact TelevisStation RS485 BusAdapter TTL Personal Computer PCI1110 1120 TelevisCompact TelevisStation BusAdapter130 150 TTL RS 485 serial interface on DIN rail for connecting the device and an RS 485 network designed for connection to Televis or ModBUS supervision...

Page 13: ... 5 2 A 1 4 hp 250Va B C D SPST 3A 250Va A SPDT 8 3 A 1 2 hp 250Va B C SPST 8 3 A 1 2 hp 250Va D SPST 5 2 A 1 4 hp 250Va if present from 55 to 140 C better than 0 5 of bottom scale 1 digit 1 or 0 1 C 2 5W 3VA 12 24Va 12 36Vc 10 or 95 240Va 10 12Va 10 50 60 Hz from instrument it is connected to 1 2 3 4 5 6 7 8 9 10 14 15 16 17 18 19 20 A B C D LINK POWER SUPPLY TTL ECHO GND RS 485 LINK Pb2 Pb1 Pb3 D...

Page 14: ...VE 1 L00 0 ECHO SLAVE 2 L00 0 ECHO SLAVE 3 L00 0 code 9IS23080 GB rel 4 08 Eliwell Controls s r l 2008 All rights reserved Eliwell Controls s r l Via dell Industria 15 Zona Industriale Paludi 32010 Pieve d Alpago BL ITALY Telephone 39 0437 986 111 Fax 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries E mail saleseliwell invensyscontrols com Technical helpline 39 0437 986 ...

Reviews: