S5-95F
Operations List
C.1.2
Supplementary Operations
Oper-
ation
(STL)
Permisible
Operands
1 RLO depend.
2 RLO affected
3 RLO reloaded
1
2
3
Typical
Execution Time
in
µ
s
On-
Ext.
board I/O
Function
A=
Formal operand
I/Q
F
T0 ... 63
T64 ... 127
C
N
Y
N
65
65
480
85
65
AND operation: scan formal operand for "1".
(Data type: BI)
AN=
Formal operand
I/Q
F
T0 ... 63
T64 ... 127
C
N
Y
N
65
65
480
85
65
AND operation: scan formal operand for "0".
(Data type: BI)
O=
Formal operand
I/Q
F,
T0 ... 63
T64 ... 127
C
N
Y
N
65
65
480
85
65
OR operation: scan formal operand for "1".
(Data type: BI)
ON=
Formaloperand
I/Q
F
T0 ... 63
T64 ... 127
C
N
Y
N
65
65
480
85
65
OR operation: scan formal operand for "0".
(Data type: BI)
AW
N
N
N
16
Combine contents of ACCU 2 and ACCU 1 through logic
AND (word operation).
Result is stored in ACCU 1. CC 1 / CC 0 are affected.
OW
N
N
N
15
Combine contents of ACCU 2 and ACCU 1 through logic
OR (word operation).
Result is stored in ACCU 1. CC 1 / CC 0 are affected.
XOW
N
N
N
16
Combine contents of ACCU 2 and ACCU 1 through logic
EXCLUSIVE OR (word operation).
Result is stored in ACCU 1. CC 1 / CC 0 are affected.
Boolean Logic Operations
for organization blocks (OB)
for program blocks (PB)
for function blocks (FB)
for sequence blocks (SB)
EWA 4NEB 812 6210-02
C-7