T3PS Series Programming Manual
90
Note
The setting will only be valid after the power has been
cycled.
Syntax
Query Syntax
:SYSTem:CONFigure:VOLTage:CONTrol
{ <NR1>|NONE|VOLTage|RRISing|RFALling|
VISolation }
:SYSTem:CONFigure:VOLTage:CONTrol?
Parameter
<NR1>
Description
0 | NONE
Local (Panel) control
1 | VOLTage
External voltage control
2 | RRISing
External resistance control; 10kΩ
or 5kΩ = Io max*, 0kΩ = Io min.
3 | RFALling
External resistance control; 10kΩ
or 5kΩ = Io min*, 0kΩ = Io max.
4 | VISolation
External voltage control
(isolated)
*The resistance value depends on
the
:SYSTem:CONFigure:CONTrol:RANGe
command.
If the range is high, then the resistance is 10kΩ,
else it is 5kΩ.
Return Parameter <NR1>
Returns the voltage control
configuration.
Example
SYST:CONF:VOLT:CONT VOLT
SYST:REB
Sets the voltage control by external voltage and
reboot the unit to active the setting.