Chapter 3 Operations Page
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
& Read/
Write
[P;Sta]
[oPEr]
Profile Status Menu
* Some parameters in the Profile Status Menu can be changed for the currently running profile,
but should only be changed by knowledgeable personnel and with caution. Changing param-
eters via the Profile Status Menu will not change the stored profile but will have an immediate
impact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be saved and will also have an
immediate impact on the running profile.
[P;Str]
[P.Str]
Profile Status
Profile Start
1 to 40
1
Instance 1
Map 1 Map 2
292
3800
0x7A
(122)
1
1
204
22001
Inst. 1
2898
Offset
+ 80
uint
RWE
[P;ACr]
[PACr]
Profile Status
Action Request
[nonE]
None (61)
[ProF]
Profile (77)
[PAUS]
Pause (146)
[rESU]
Resume (147)
[`End]
Terminate (148)
[step]
Step (89)
None
Instance 1
Map 1 Map 2
306
3820
0x7A
(122)
1
0xB (11)
205
22011
Inst. 1
2920
Offset
+ 80
uint
RW
[`StP]
[ StP]
Profile Status
Active Step
View the currently running
step.
1 to 40
0 (none)
Instance 1
Map 1 Map 2
296
3806
0x7A
(122)
1
4
- - - -
22004
Inst. 1
2906
Offset
+ 80
uint
R
[S;typ]
[S.typ]
Profile Status
Active Step Type
View the currently running
step type.
[UStP]
Unused Step
(50)
[``ti]
Time (143)
[rAtE]
Rate (81)
[SoAH]
Soak (87)
[w;e]
Wait for Event
(144)
[w;pr]
Wait for Pro-
cess(209)
[CloC]
Wait for Time
(1543)
[``JL]
Jump Loop (116)
[`End]
End (27)
- - - -
Instance 1
Map 1 Map 2
- - - - 3824
0x7A
(122)
1
0xD (13)
- - - -
22013
Inst. 1
2924
Offset
+ 80
uint
R
[t;SP1]
[tg.SP]
Profile Status
*Target Set Point Loop 1
View or change the target
set point of the current
step.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Instance 1
Map 1 Map 2
- - - - 3822
0x7A
(122)
1
0xC (12)
- - - -
22012
- - - - uint
RW
[P;SP1]
[P.SP1]
Profile Status
Produced Set Point 1
Display the current set
point, even if the profile is
ramping.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Instance 1
Map 1 Map 2
297
3808
- - - -
- - - -
22005
Inst. 1
2908
Offset
+ 80
float
R
[hour]
[hour]
Profile Status
Hours Remaining
0 to 99
0.0
Instance 1
Map 1 Map 2
- - - - - - - -
- - - -
- - - -
22078
- - - - - - - -
[min]
[Min]
Profile Status
Minutes Remaining
0 to 59
0.0
Instance 1
Map 1 Map 2
- - - - - - - -
- - - -
- - - -
22077
- - - - - - - -
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set