KLIC-FJ vT
Technical Support:
32
111, 140, 169
1 Bit
I
C - W - -
DPT_Start
0/1
[Ix] Presence: Slave Input
0 = Nothing; 1 = Detection from
slave device
112, 141, 170
2 Bytes
I
C - W - -
DPT_TimePeriodSec
0 - 65535
[Ix] Presence: Waiting Time
0-65535 s.
113, 142, 171
2 Bytes
I
C - W - -
DPT_TimePeriodSec
0 - 65535
[Ix] Presence: Listening Time
1-65535 s.
114, 143, 172
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] Presence: Enable
According to parameters
115, 144, 173
1 Bit
I
C - W - -
DPT_DayNight
0/1
[Ix] Presence: Day/Night
According to parameters
116, 145, 174
1 Bit
O
C R - T -
DPT_Occupancy
0/1
[Ix] Presence: Occupancy State
0 = Not Occupied; 1 = Occupied
117, 146, 175
1 Bit
I
C - W - -
DPT_Start
0/1
[Ix] External Motion Detection
0 = Nothing; 1 = Motion detected by
an external sensor
118, 123, 128, 147, 152,
157, 176, 181, 186
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Ix] [Cx] Detection State (Scaling)
0-100%
119, 124, 129, 148, 153,
158, 177, 182, 187
1 Byte
O
C R - T -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Ix] [Cx] Detection State (HVAC)
Auto, Comfort, Standby, Economy,
Building Protection
120, 125, 130, 149, 154,
159, 178, 183, 188
1 Bit
O
C R - T -
DPT_Switch
0/1
[Ix] [Cx] Detection State (Binary)
Binary Value
121, 126, 131, 150, 155,
160, 179, 184, 189
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] [Cx] Enable Channel
According to parameters
122, 127, 132, 151, 156,
161, 180, 185, 190
1 Bit
I
C - W - -
DPT_Switch
0/1
[Ix] [Cx] Force State
0 = No Detection; 1 = Detection
191, 195, 199
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Ix] Current Temperature
Temperature Sensor Value
192, 196, 200
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm; 1 = Alarm
193, 197, 201
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm; 1 = Alarm
194, 198, 202
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm; 1 = Alarm
203
1 Byte
I/O
C R W T U
DPT_SceneControl
0-63; 128-191
[AC] Scene
0 - 63 (Execute 1 - 64); 128 - 129
(Save 1 - 64)
204
1 Byte
I
C - W - -
DPT_HVACContrMode
0=Auto
1=Heat
3=Cool
9=Fan
14=Dry
[AC] Mode
0 = Automatic; 1 = Heating; 3 =
Cooling; 9 = Fan; 14 = Dry
205
1 Byte
O
C R - T -
DPT_HVACContrMode
0=Auto
1=Heat
3=Cool
9=Fan
14=Dry
[AC] Mode (Status)
0 = Automatic; 1 = Heating; 3 =
Cooling; 9 = Fan; 14 = Dry
206
1 Bit
I
C - W - -
DPT_Heat_Cool
0/1
[AC] Simplified Mode
0 = Cooling; 1 = Heating
207
1 Bit
O
C R - T -
DPT_Heat_Cool
0/1
[AC] Simplified Mode (Status)
0 = Cooling; 1 = Heating
208
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] On/Off
0 = Off; 1 = On