111, 140, 169

 

1 Bit

 

I

 

C - W - -

 

DPT_Start

 

0/1

 

[Ix] Presence: Slave Input

 

0 = Nothing; 1 = Detection from 

slave device

 

112, 141, 170

 

2 Bytes

 

I

 

C - W - -

 

DPT_TimePeriodSec

 

0 - 65535

 

[Ix] Presence: Waiting Time

 

0-65535 s.

 

113, 142, 171

 

2 Bytes

 

I

 

C - W - -

 

DPT_TimePeriodSec

 

0 - 65535

 

[Ix] Presence: Listening Time

 

1-65535 s.

 

114, 143, 172

 

1 Bit

 

I

 

C - W - -

 

DPT_Enable

 

0/1

 

[Ix] Presence: Enable

 

According to parameters

 

115, 144, 173

 

1 Bit

 

I

 

C - W - -

 

DPT_DayNight

 

0/1

 

[Ix] Presence: Day/Night

 

According to parameters

 

116, 145, 174

 

1 Bit

 

O

 

C R - T -

 

DPT_Occupancy

 

0/1

 

[Ix] Presence: Occupancy State

 

0 = Not Occupied; 1 = Occupied

 

117, 146, 175

 

1 Bit

 

I

 

C - W - -

 

DPT_Start

 

0/1

 

[Ix] External Motion Detection

 

0 = Nothing; 1 = Motion detected by 

an external sensor

 

118, 123, 128, 147, 152, 

157, 176, 181, 186

 

1 Byte

 

O

 

C R - T -

 

DPT_Scaling

 

0% - 100%

 

[Ix] [Cx] Detection State (Scaling)

 

0-100%

 

119, 124, 129, 148, 153, 

158, 177, 182, 187

 

1 Byte

 

O

 

C R - T -

 

DPT_HVACMode

 

1=Comfort 

2=Standby 

3=Economy 

4=Building 

Protection

 

[Ix] [Cx] Detection State (HVAC)

 

Auto, Comfort, Standby, Economy, 

Building Protection

 

120, 125, 130, 149, 154, 

159, 178, 183, 188

 

1 Bit

 

O

 

C R - T -

 

DPT_Switch

 

0/1

 

[Ix] [Cx] Detection State (Binary)

 

Binary Value

 

121, 126, 131, 150, 155, 

160, 179, 184, 189

 

1 Bit

 

I

 

C - W - -

 

DPT_Enable

 

0/1

 

[Ix] [Cx] Enable Channel

 

According to parameters

 

122, 127, 132, 151, 156, 

161, 180, 185, 190

 

1 Bit

 

I

 

C - W - -

 

DPT_Switch

 

0/1

 

[Ix] [Cx] Force State

 

0 = No Detection; 1 = Detection

 

191, 195, 199

 

2 Bytes

 

O

 

C R - T -

 

DPT_Value_Temp

 

-273.00º - 670433.28º

 

[Ix] Current Temperature

 

Temperature Sensor Value

 

192, 196, 200

 

1 Bit

 

O

 

C R - T -

 

DPT_Alarm

 

0/1

 

[Ix] Overcooling

 

0 = No Alarm; 1 = Alarm

 

193, 197, 201

 

1 Bit

 

O

 

C R - T -

 

DPT_Alarm

 

0/1

 

[Ix] Overheating

 

0 = No Alarm; 1 = Alarm

 

194, 198, 202

 

1 Bit

 

O

 

C R - T -

 

DPT_Alarm

 

0/1

 

[Ix] Probe Error

 

0 = No Alarm; 1 = Alarm

 

203

 

1 Byte

 

I/O

 

C R W T U

 

DPT_SceneControl

 

0-63; 128-191

 

[AC] Scene

 

0 - 63 (Execute 1 - 64); 128 - 129 

(Save 1 - 64)

 

204

 

1 Byte

 

I

 

C - W - -

 

DPT_HVACContrMode

 

0=Auto 

1=Heat 

3=Cool 

9=Fan 

14=Dry

 

[AC] Mode

 

0 = Automatic; 1 = Heating; 3 = 

Cooling; 9 = Fan; 14 = Dry

 

205

 

1 Byte

 

O

 

C R - T -

 

DPT_HVACContrMode

 

0=Auto 

1=Heat 

3=Cool 

9=Fan 

14=Dry

 

[AC] Mode (Status)

 

0 = Automatic; 1 = Heating; 3 = 

Cooling; 9 = Fan; 14 = Dry

 

206

 

1 Bit

 

I

 

C - W - -

 

DPT_Heat_Cool

 

0/1

 

[AC] Simplified Mode

 

0 = Cooling; 1 = Heating

 

207

 

1 Bit

 

O

 

C R - T -

 

DPT_Heat_Cool

 

0/1

 

[AC] Simplified Mode (Status)

 

0 = Cooling; 1 = Heating

 

208

 

1 Bit

 

I

 

C - W - -

 

DPT_Switch

 

0/1

 

[AC] On/Off

 

0 = Off; 1 = On

 

Summary of Contents for KLIC-FJ vT

Page 1: ...KLIC FJ vT KNX RWB Gateway for Fujitsu AC Units USER MANUAL ZCLFJVT Application program version 1 1 User manual edition 1 1 _a www zennio com...

Page 2: ...1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Inputs 8 2 2 1 Binary Input 8 2 2 2 Temperature Probe 8 2 2 3 Motion Detector 8 2 3 Logic Functions 9 2 4 A C Gateway 10 2 4 1 Config...

Page 3: ...itored and periodically sent to the KNX bus to inform other devices The most outstanding features of KLIC FJ vT are Bidirectional control of Fujitsu A C units through the connection wires provided by...

Page 4: ...utton will set the device into the programming mode making the associated LED 1 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode...

Page 5: ...lease refer to the device Datasheet bundled in the device packaging and also available at www zennio com 1 3 START UP AND POWER LOSS Depending on the configuration some specific actions will be perfor...

Page 6: ...ons related to interfacing with the A C unit and to the management of the climate control system ETS PARAMETERISATION After importing the corresponding database in ETS and adding the device into the t...

Page 7: ...f Status allow switching on value 1 and off value 0 the A C unit or reading the current status respectively AC Temperature Setpoint and AC Temperature Setpoint Status allow setting the desired tempera...

Page 8: ...Detector for the connection of a motion detector from Zennio 2 2 1 BINARY INPUT Please refer to the Binary Inputs user manual available in the KLIC FJ vT product section at the Zennio website www zenn...

Page 9: ...ecution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after exe...

Page 10: ...n the A C unit Moreover KLIC FJ vT allows configuring several advanced functions Control configuration which allows establishing the type of master slave control desired to KLIC FJ vT Error type confi...

Page 11: ...rrent state When KLIC FJ vT is notified about a change it updates the status objects and sends them to the KNX bus In addition KLIC FJ vT provides an error management function see section which allows...

Page 12: ...controllers in the installation When selecting this option the parameter Number of Controllers shows up with the following options 1 Controller KLIC as Master KLIC FJ vT will be configured as a master...

Page 13: ...ujitsu define two error types Type A RAC non inverter units RAC inverter units till Typ A models VRF J S V series units Type B RAC inverter units new Typ G models VRF J S V series units Important KLIC...

Page 14: ...ble by default it is possible to commute and to verify the current operation mode through the following 1 Bit objects which get enabled after activating this parameter Simplified Mode which allows swi...

Page 15: ...Y 5 or to X 5 if Y 5 Status object will be updated to the last setpoint temperature value received by the A C unit after a complete communication cycle and will be sent to KNX bus every time that its...

Page 16: ...value Notes If Minimum Maximum limits will not be taken in account in Auto mode due to the incongruity In this case default values will be used These parameters only can be set as integer values in E...

Page 17: ...uring run time Furthermore the available parameters in ETS are Initial Operation Time Keep current value option enabled by default which keep the previous value Set value allows establishing an initia...

Page 18: ...ff Object Polarity sets the polarity of the above object 0 Activate 1 Deactivate o 0 Deactivate 1 Activate Automatic Off Delay sets the time in seconds KLIC FJ vT waits before switching the AC machine...

Page 19: ...ailable levels To that end KLIC FJ vT provides a percentage control In addition KLIC FJ vT allows activating the automatic fan speed mode in case of being available in the unit Referring to the user m...

Page 20: ...levels Automatic Control Values Status Values Level Sent to the Unit 0 0 Automatic 1 25 25 1 minimum 26 50 50 2 51 75 75 3 76 100 100 4 maximum Table 2 Fan speed four levels Individual Object for Aut...

Page 21: ...for better distribution of the airflow in case of being available in the unit Referring to the user manual of the A C unit is advisable prior to setting up these options ETS PARAMETRISATION After ena...

Page 22: ...ition 3 61 80 80 Position 4 81 100 100 Position 5 Table 4 Flap position five positions Swing available sets whether the A C unit incorporates a swing function If enabled value 0 of the AC Vertical Hor...

Page 23: ...n or Dry Fan speed Last Automatic or any of the available fan speeds 1 4 Horizontal flaps if set it can be selected Last Swing if available Auto if the automatic flap position control is available or...

Page 24: ...allows defining a set of statuses in terms of On Off mode fan speed etc that KLIC FJ vT will send to the A C unit whenever it receives the corresponding scene values from the KNX bus ETS PARAMETRISATI...

Page 25: ...e or any of the available flap positions 1 5 Vertical flaps No change Swing if available Auto if the automatic flap position control is available or any of the available flap positions 1 5 Setpoint No...

Page 26: ...gured if it does not locate any of the controllers error 0012 will be notified If KLIC FJ vT is configured as master by selecting only 1 controller and there is a master remote wired controller instal...

Page 27: ...error in A C machine AC AC Unit Error Error Code 14 Byte object which provides error code In case the A C unit reports an error the former object will send a value of 1 while the latter will report t...

Page 28: ...DPT_Value_2_Count 32768 32767 DPT_Value_Tempo 273 00 670760 00 66 67 68 69 70 71 72 73 4 Bytes I C W DPT_Value_4_Count 2147483648 2147483647 LF 4 Byte Data Entry x 4 Byte Data Entry 74 75 76 77 78 79...

Page 29: ...Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Short Press Darker Decrease Brightness 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Short...

Page 30: ...1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Down Shutter Sending of 1 Down 1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Up Down Shutter Switching 0 1 Up Down 1 Bit C T DPT_Step 0 1 Ix Long Press Stop...

Page 31: ...ng Press Release Stop Shutter Release Stop Shutter 89 95 101 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Dimming Status Input 0 100 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Shutter Status Input 0...

Page 32: ...Protection 120 125 130 149 154 159 178 183 188 1 Bit O C R T DPT_Switch 0 1 Ix Cx Detection State Binary Binary Value 121 126 131 150 155 160 179 184 189 1 Bit I C W DPT_Enable 0 1 Ix Cx Enable Chann...

Page 33: ...Automatic Off Speed 1 217 1 Bit O C R T DPT_Enable 0 1 AC Fan Automatic Status 0 Automatic On 1 Automatic Off 1 Bit O C R T DPT_Enable 0 1 AC Fan Automatic Status 0 Automatic Off 1 Automatic On 218 1...

Page 34: ...Deactivate 229 1 Bit O C R T DPT_Switch 0 1 AC Automatic Off Status 0 Deactivated 1 Activated 1 Bit O C R T DPT_Switch 0 1 AC Automatic Off Status 0 Activate 1 Deactivate 230 2 Bytes I C W DPT_TimePe...

Page 35: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Reviews: