Name
Range
Step Default Protection
functions
Description
Starts
when
hot
1…100
1
2
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The number of allowed starts per x hours for a hot motor.
Starts in
hours
1…100h
1h
1h
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The number of hours when the parameters of the number of
allowed starts (hot and cold) apply.
Min time
betw.
starts
0.1…600.0s
0.1s
20.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The minimum time between starts or start attempts.
Table. 5.3.21 - 164. Output signals of the N> function.
Name
Range Step Default
Description
N> Alarm
on
0: Not
active
1:
Active
1
0
Alarm output of the function. This signal activates when there is one (1) start
available for the motor.
N> Inhibit
on
0: Not
active
1:
Active
1
0
Inhibit output of the function. This signal activates when all available starts have been
used and the motor is not allowed to start before the starts counter has one (1) or
more starts available.
N>
BLOCKED
0: Not
active
1:
Active
1
0
Blocked output of the function. This signal activates when the function is activated
but is blocked from operating normally.
Events and registers
The frequent start protection function (abbreviated "FSP" in event block names) generates events from
the detected motor status. The data register is available, based on the changes in the events.
Table. 5.3.21 - 165. Event codes.
Event number
Event channel
Event block name
Event code
Description
3584
56
FSP1
0
Alarm ON
3585
56
FSP1
1
Alarm OFF
3586
56
FSP1
2
Inhibit ON
3587
56
FSP1
3
Inhibit OFF
3588
56
FSP1
4
Blocked ON
3589
56
FSP1
5
Blocked OFF
The function registers its operation into the last twelve (12) time-stamped registers. The table below
presents the structure of the function's register content.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
239