31
Unloading robot logic
The unloading robot will make the decision to unload (or not unload) a certain rack based
on the following flowchart.
Here, as previously described, the FLAG “Automatic Unloading Authorized” functions as
an override, enabling the robot to unload a rack on which there is a pharma-alarm.
If an unauthorized rack ends up in the unloading position, an alarm/notification (A5) is
raised that should be confirmed by the operator. Confirming this notification will send the
rack to the manual unloading position at the loading side.
RACK
EMPTY
NOT EMPTY
Status: pharma-alarm FALSE
Processed conform
Status: pharma-alarm or
processed non-conform
FLAG Automatic
Unloading Authorized =
FALSE
FLAG Automatic
Unloading Authorized =
FALSE
Continue to loading side robot
IF Cycle ID (n)=/= Cycle ID (n-1)
(compare with last one in shift
register)
UNLOAD & clear
relevant data
ADD Cycle ID (n) to
shift register
Empty tubs for cycle
separation
Alarm/notification (A5): orange alert
+
Change of direction after
acknowledgement
of the alarm to
manual unloading – loading side