HGL Manual
5.0 PQconnect Connectivity
28
Register Map
Write
Parameters:
Table 15: Network Interface INPUT/Setpoint Register Map
Parameter Name
I/O Reg
Address
Offset
Direction
Data Values and Examples
Description
PARAM_USER_CMD_REQ
500
Input
9 = Save Current Values to Flash
21 = Set User Access
25 = Set Access to Tech Access
(access key needs to be set to
0825 for key A and 2014 for key B)
150 = Load Values from Flash
200 = Restore Defaults to Flash
TRACE_GO_DONE
501
Input
0 = Capture Done
1 = Start Capture
Trace Data points for
waveforms
SYS_RESET
502
Input
0 = No Command
1 = Reset Contactor Closed
Reset contactor
PARAM_KEY_A
503
Input
Enter Key A
Read/write parameters under
Tech Access
PARAM_KEY_B
504
Input
Enter Key B
CT_RATIO
505
Input
XXXX:5 where XXXX is the primary
turns count of the CT
1000 = 1000:5
Range 5 to 10000
Dual Tuned Circuit Current
Transformer (CT) ratios*
Note:
Only required for units
with dual tuned circuits
SYS_CONTROL_MODE
510
Input
0 = Always Open
1 = Always Closed
DEFAULT:
2= Auto load
3 = Auto kVAR
4 = External
5 = No contactor
Contactor control; keep
contactor always off/on, auto
turn on/off based on desired
load or kVAR, external relay
input. *
SYS_AUTO_CONTACTOR_CLOSED
511
Input
0 = Disable
DEFAULT:
1 = Enable
Contactor auto reclose, this
will attempt to reclose the
contactor after it has been
open through a status
condition. *
RATED_CURRENT
520
Input
1000 = 100 A
Range: 3 to 1500 A
Filter rated current*
RATED_VOLTAGE
521
Input
4800 = 480Vrms
Range: 120 to 690 Vrms
Filter rated voltage*
RATED_FREQUENCY
522
Input
50 = 50 Hz
60 = 60 Hz
Filter rated frequency*