5.0 PQconnect Connectivity
35
Read Parameters:
Table 24: Network Interface OUTPUT/Feedback Register Map
Parameter Name
I/O Reg
Address Offset
Direction
Data Values and
Examples
Description
CNT_CLOSED
200
Output
0 = Contactor Closed
1 = Contactor Open
Indicates the status of the
Filters tuned circuit contactor.
STATUS_FILTER_A
210
Output
0 = Disabled
To Enable desired
status detections,
enter bit mask from
table by converting to
decimal
Range: 0 to 65535
Reference Table 18 above for
filter status detections.
STATUS_FILTER_B
211
Output
STATUS_FILTER_A_ENABLE_RO
220
Output
STATUS_FILTER_B_ENABLE_RO
221
Output
STATUS_FILTER_A_RELAY_ACTION_RO
230
Output
STATUS_FILTER_B_RELAY_ACTION_RO
231
Output
STATUS_FILTER_A_CNT_ACTION_RO
240
Output
STATUS_FILTER_B_CNT_ACTION_RO
241
Output
STATUS_LINE
212
Output
Reference Table 19 above for
line status detections.
STATUS_LINE_ENABLE_RO
222
Output
STATUS_LINE_RELAY_ACTION_RO
232
Output
STATUS_LINE_CNT_ACTION_RO
242
Output
STATUS_FILTER_LOAD
213
Output
Reference Table 20 above for
load status detections.
STATUS_FILTER_LOAD_ENABLE_RO
223
Output
STATUS_FILTER_LOAD_RELAY_ACTION_R
O
233
Output
STATUS_FILTER_LOAD_CNT_ACTION_RO
243
Output
SYS_CONTROL_MODE_RO
250
Output
0 = Always Open
1 = Always Closed
DEFAULT:
2= Auto
load
3 = Auto kVAR
4 = External Control
Input
5 = No contactor
Contactor control; keep
contactor always off/on, auto
turn on/off based on desired
load percentage or kVAR,
external relay input.
TRACE_GO_DONE_RO
251
Output
0 = Capture Done
1 = Start Capture
Indicates waveform data
SYS_AUTO_FAULT_RESET_RO
252
Output
0 = Disabled
1 = Enabled
Displays auto contactor reset
CT_RATIO_RO
253
Output
XXXX:5 where XXXX
is the primary turns
count of the CT
1000 = 1000:5
Range 5 to 10000
Dual Turned Circuit Current
Transformer (CT) ratios
Note: Only required for units
with two tuned circuits
PARAM_ACCESS_LEVEL_RO
254
Output
0 = Base access
1 = Tech access
Level of parameter access to
read and/or change parameter
inputs