HGL Manual
5.0 PQconnect Connectivity
36
Read Parameters:
Table 25: Network Interface OUTPUT/Feedback Register Map
Parameter Name
I/O Reg
Address
Offset
Direction
Data Values and
Examples
Description
CNT_STATUS
257
Output
0 = Contactor Closed
1 = Contactor Open
Contactor command status
RATED_VOLTAGE_RO
260
Output
4800 = 480Vrms
Range: 120 to 690 Vrms
Filter rated voltage
RATED_CURRENT_RO
261
Output
1000 = 100 A
Range: 3 to 1500 Arms
Filter rated current
RATED_FREQUENCY
262
Output
50 = 50 Hz
60 = 60 Hz
Filter rated frequency
CNT_CLOSE_LOAD_THRESHOLD_RO 270
Output
DEFAULT:
30 = 30%
Range: 10 to 100 %
Contactor close threshold based on the
load *
CNT_CLOSE_LOAD_HYSTERESIS_RO 271
Output
DEFAULT:
5 = 5%
Range: 2 to 50 %
Contactor will open when it reaches the
hysteresis percentage
CNT_CLOSE_KVAR_THRESHOLD_RO 272
Output
100 = 100 kVAR
Range: 0 to 1000 kVAR
Contactor close threshold for kVAR
control*
CNT_CLOSE_KVAR_HYSTERESIS_RO 273
Output
DEFAULT:
10 = 10%
Range: 5 to 100 %
Contactor will open when it reaches the
hysteresis percentage
CNT_CLOSE_DELAY_RO
274
Output
DEFAULT:
5 = 5 seconds
Range: 1 to 3600 seconds
Displays set value of contactor closed
delay time
CNT_OPEN_DELAY_RO
275
Output
DEFAULT:
5 = 5 seconds
Range: 1 to 3600 seconds
Displays set value of contactor open
delay time
CNT_AUTO_RECLOSE_DELAY_RO
280
Output
DEFAULT:
300 = 300
seconds
Range: 120 to 3600
seconds
Indicates contactor auto reclose delay
time
CNT_POWER_ON_DELAY_RO
281
Output
DEFAULT:
0 = 0 seconds
Range: 0 to 3600 seconds
Indicates contactors power on delay
time
CNT_AUTO_RECLOSE_ATTEMPS_RO 282
Output
DEFAULT:
5 = 5 attempts
Range 1 to 15
Indicates set value of attempts
CNT_AUTO_RECLOSE_TIMESPAN_R
O
283
Output
DEFAULT:
1800 = 1800
seconds
Range: 300 to 3600
seconds
Displays timespan of contactor to
reclose
CNT_AUTO_RECLOSE_TIMER_RO
284
Output
Displays count down time for contactor
to reclose
SYS_CNT_MIN_OFF_TIME_RO
285
Output
DEFAULT:
60 = 60
seconds
Range: 30 to 300 seconds
Minimum time off for contactor re-
closures
SYS_CNT_MIN_OFF_TIMER
286
Output
Displays count down time for contactor
re-closures
MB_SLAVE_ADDRESS_RO
300
Output
DEFAULT:
= 10
Range: 0 to 255
Modbus slave address
MB_BAUD_RATE_RO
301
Output
960 = 9600 moderate
3840 = 38400 baud rate
DEFAULT
: 11520 =
115200 baud rate
Modbus baud rate