CDE360 Vector Control AC Drive Chapter 8 Communication Protocol
5.Pulse output control: (Write-only)
Command address
Command comment
6404H
0x0
~
0x7FFF corresponding to 0%
~
100%
6.Analog output AO1 control: (Write-only)
Command address
Command comment
6405H
0x0
~
0x7FFF corresponding to 0%
~
100%
7.Analog output AO2 control: (Write-only)
Command address
Command comment
6406H
0x0
~
0x7FFF corresponding to 0%
~
100%
8.AC drive fault description (Read-only)
AC drive error address
AC drive error info
6407H
0: No error
1: Hardware accelerate over voltage
2: Hardware decelerate over voltage
3: Hardware constant speed over voltage
4: Software accelerate over voltage
5: Software decelerate over voltage
6: Software constant speed over voltage
7: Under voltage
8: Hardware accelerate over current
9: Hardware decelerate over current
10: Hardware constant speed over current
11: Software accelerate over current
12: Software decelerate over current
13: Software constant speed over current
14: Module accelerate error
15: Module decelerate error
16: Module constant speed error
17: Rectifier bridge over temperature
18: Inverter bridge over temperature
19: Input osting - phase