26 - 40
021774/07/14
6.3.2 Command BR
<id>BR<parameter><CR>
Select baud rate
Access:
Read / write
Description:
The command BR is used to select the required baud rate.
Parameter description:
Parameter
Description
12
1200baud (8n1)
24
2400baud (8n1)
48
4800baud (8n1)
96
9600baud (8n1)
192
19200baud (8n1)
384
38400baud (8n1)
576
57600baud (8n1)
1152
115200baud (8n1)
Value range:
12 / 24 / 48 / 96 / 192 / 384 / 576 / 1152
Initial value:
96
6.3.3 Command CI
<id>CI<parameter><CR>
Selection of command interpreter
Access:
Read / write
Description:
The requested command interpreter is set by command CL.
Remark:
If the identification number (ID) is > 98, it is set to 0 automatically
with the change-over to the THIES interpreter!
Remark:
If the identification number (ID) equals 0, a change-over to the
MODBUS-RTU-interpreter is not possible!
Parameter description:
Parameter
Description
0
THIES
1
MODBUS RTU
Value range:
0 to 1
Initial value:
0