FL4000
45
Register
Address
(Hex)
Parameter
Function
Data
Type
Data Range Access
0x003F
Line Voltage
Line input voltage * 10.0
Numeric
Value *
10
50 - 360
R
0x0040 –
0x0046
Reserved N/A
N/A
N/A N/A
0x0047
Real Time Clock
Year, Month
Read/Set year and month
of RTC
Numeric
Value
1 –99 year,
1– 12
month
R/W
0x0048
Real Time Clock
Day, Hour
Read/Set day and hour of
RTC
Numeric
Value
1 – 31 day,
0 – 23 hour
R/W
0x0049
Real Time Clock
Minute, Second
Read/Set minutes and
seconds of RTC
Numeric
Value
0 – 59
minutes
0 – 59
seconds
R/W
0x004A –
0x0059
Reserved N/A
N/A
N/A N/A
0x005A
TEST LAMP Test
Mode
Set/Reset TEST LAMP
test mode. 0 = Normal
Mode. 1 = Test Mode.
Numeric
Value
0 - 1
R/W
0x005B
Alarm Delay
Read/Set Alarm Delay
Numeric
Value
0 – 30
R/W
0x005C –
0x0090
Reserved N/A
N/A
N/A N/A
0x009A
Power Cycled
Flag
Time Reset After power
Cycled
Numeric
Value
0 = Time
not Reset, 1
= Time
Reset
R
0x009B –
0x009F
Reserved N/A
N/A
N/A N/A
0x00A0
Event Index
Index of Logged Events
Numeric
Value
0 - 9
R/W
0x00A1
Running Time Hi
Running Time Hi for
Warning Event log entries
Numeric
Value
0 - 65535
R
0x00A2
Running Time Low Running Time Low for
Warning Event log entries
Numeric
Value
0 - 65535
R
0x00A3
Clock Time Hi
Hi byte = year, Lo byte
month: Warning clock
time
Numeric
Value
1 –99 year,
1– 12
month
R
0x00A4
Clock Time Mid
Hi byte = Day, Lo byte
Hour: Warning clock time
Numeric
Value
1 – 31 day,
0 – 23 hour
R
0x00A5
Clock Time Low
Hi byte = Minute, Lo byte
second: Warning clock
time
Numeric
Value
0 – 59
minutes
0 – 59
seconds
R
0x00A6 Reserved
Reserved
Numeric
Value
0 R