FL4000
50
4.10.10
COM1 Baud Rate (0x000B)
A read command returns the current baud rate for COM1 channel. A write command changes
the baud rate to the requested values. Valid settings are shown in Table 33.
Factory default is
19,200 baud.
Table 33: Com1 Baud Rate
Baud Rate
Value
Access
2,400
0
Read / Write
4,800
1
Read / Write
9,600
2
Read / Write
19,200
3
Read / Write
38,400
4
Read / Write
NOTE:
If the baud rate is not in range, an Illegal Data Value (03) is returned. By grounding the
RESET input during the first 1 second of the power up cycle, the FL4000 Baud Rate
will default to 19.2K. The baud rate will be set to a default of 19.2K when the red and
green LED’s flash alternately after approximately 1 second, at which time the RESET
input can be released from ground.
4.10.11
COM1 Data Format (0x000C)
A read command returns the current data format for COM1 channel. Write command changes
the data format to the requested values. Valid settings are shown in Table 34. Default format is
8-N-1.
Table 34: Selectable Data Formats
Format
Parity
Stop
Data Bits
Value
Access
8-N-1
None
1
8
0
Read / Write
8-E-1
Even
1
8
1
Read / Write
8-O-1
Odd
1
8
2
Read / Write
8-N-2
None
2
8
3
Read / Write
NOTE:
If the data format is not in range, an Illegal Data Value (03) is returned. By grounding
the RESET input during the first 1 second of the power up cycle, the FL4000 Data
Format will default to 8-N-1. The Data Format will be set to a default of 8-N-1 when the
red and green LED’s flash alternately after approximately 1 second, at which time the
RESET input can be released from ground.
4.10.12 COPM
Counts
Sensor 1 (0x000D)
A read indicates the number of COPM Faults that have occurred for sensor 1 in the FL4000.
Please refer to Section 2.4.2 for more information on COPM and Section 6.0 for
troubleshooting tips.
4.10.13 COPM
Counts
Sensor 2 (0x000E)
A read indicates the number of COPM Faults that have occurred for sensor 2 in the FL4000.
Please refer to Section 2.4.2 for more information on COPM and Section 6.0 for
troubleshooting tips.