Commands
2597
78 2013-
02
103
Single Read Fixcode (SF)
Only one attempt is made to read fixcode. The specified length of the fixcode
depends on the data carrier type.
Single write fix code (SX)
Only possible with data carrier types IPC11 and IPC14.
Only one attempt is made to write a fix code. The specified length of the fix code is
always 5 bytes
Single get configuration (SG)
Only possible with data carrier types IPC03 and IPC12.
Only one attempt is made to read a word in the configuration area ("protection
word" or "control word") from address <ConfAddr>.
Single write configuration (SC)
Only one attempt is made to write a word to the configuration area ("protection
word" or "control word") from address <ConfAddr>.
Password mode must be activated in the read head to write to the configuration
area.
Fill Data Carrier (S#)
The data carrier is filled with <WordNum> data blocks described by fill signs
<FillSign> from the specified block address <WordAddr>.
Get State (GS)
This command is used to read out permanently stored read/write head settings.
Command:
SF
Response:
<Status><Data>
Command:
SX
<FixType> <FixLen> <Data>
Response:
<Status>
Command:
SG
<ConfAddr>
Response:
<Status><Data>
Command:
SC
<ConfAddr><Data>
Response:
<Status>
Command:
S#
<WordAddr><WordNum><FillSign>
Response:
<Status>
Command:
GS
Response:
TT: <TagType>, TO:<Timeout>, BD:<Baud>